Pilot Protection Based on Amplitude of Directional Travelling Wave for Voltage Source Converter-High Voltage Direct Current (VSC-HVDC) Transmission Lines

被引:9
|
作者
Jiang, Lingtong [1 ]
Chen, Qing [1 ]
Huang, Wudi [1 ]
Wang, Lei [2 ]
Zeng, Yu [1 ]
Zhao, Pu [3 ]
机构
[1] Shandong Univ, Minist Educ, Key Lab Power Syst Intelligent Dispatch & Control, Jinan 250061, Shandong, Peoples R China
[2] Weifang Elect Power Co, Weifang 261000, Shandong, Peoples R China
[3] Jinan Elect Power Co, Jinan 250061, Shandong, Peoples R China
关键词
directional pilot protection; VSC-MTDC; time difference; stationary wavelet transform; phase-mode transformation; DC FAULTS; SCHEME;
D O I
10.3390/en11082021
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper presents a novel pilot protection scheme of DC cable line in voltage-source-converter (VSC) based multi-terminal DC (MTDC) grids, which utilizes a novel phase-mode transformation to decouple the bipolar DC cable current into six mode and it uses the stationary wavelet transform to extract the modulus maxima of fault initial traveling waves current (FITWC). With accurate amplitude and polarities of the FITWC being collected from the fault-detection devices located at each terminal, the proposed scheme can correctly determine the faulty segment and the faulty pole. In this paper, the ratio of amplitudes between sixth mode forward and backward travelling wave currents is used to judge the faulty segment and the polarity of fifth mode forward travelling wave current is used to identify the faulty pole. A four-terminal VSC-based MTDC grid was built in PSCAD/EMTDC to evaluate the performance of the fault-protection scheme. Simulation results for different cases demonstrate that the proposed protection scheme is robust against noise, and has been tested successfully for fault resistance of up to 400 Omega. Since the scheme merely needs the characteristics of FITWCs, the practical difficulties of detecting subsequent travelling waves are avoided. Moreover, only the state signal is needed to send to the other side in proposed scheme, so low communication speed can satisfy the requirement of relay protection and it does not need the data synchronization seriously.
引用
收藏
页数:15
相关论文
共 11 条
  • [1] Novel travelling wave directional pilot protection for VSC-HVDC transmission line
    Wang, Dong
    Yu, Dachuan
    Yang, Haishan
    Hou, Mengqian
    Guo, Yifei
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2020, 14 (09) : 1705 - 1713
  • [2] Research on an Improved Protection Principle Based on Differential Voltage Traveling Wave for VSC-HVDC Transmission Lines
    Li, Botong
    Lv, Mingrui
    Li, Bin
    Xue, Shimin
    Wen, Weijie
    IEEE TRANSACTIONS ON POWER DELIVERY, 2020, 35 (05) : 2319 - 2328
  • [3] Operation of Multi-Terminal Voltage Source Converter (VSC-HVDC) Transmission System with Ripple Mitigation
    Silliman, Ahmed S.
    Helal, Ibrahim
    Emarah, Adel
    2017 NINETEENTH INTERNATIONAL MIDDLE-EAST POWER SYSTEMS CONFERENCE (MEPCON), 2017, : 1505 - 1511
  • [4] A pilot directional protection based on low frequency voltage variable quantity for LCC-HVDC transmission lines
    Chen, Yu
    Wen, Minghao
    Wang, Zhen
    Yin, Xianggen
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2023, 145
  • [5] Fault detection for offshore wind farm connected to onshore grid via voltage source converter-high voltage direct current
    Perveen, Rehana
    Kishor, Nand
    Mohanty, Soumya R.
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2015, 9 (16) : 2544 - 2554
  • [6] Pilot protection for flexible HVDC transmission lines based on transient voltage ratio characteristics
    Wang, Zhijie
    Li, Haifeng
    Jin, Haotian
    Liu, Hainan
    Liang, Yuansheng
    Wang, Gang
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2024, 162
  • [7] The overhead transmission line protection scheme for the voltage-source converter-based HVDC grids
    Wang, Yanting
    Zhang, Baohui
    Fan, Xinkai
    JOURNAL OF ENGINEERING-JOE, 2019, (16): : 674 - 679
  • [8] A novel linear regression density peak clustering-based transmission line protection for line-commuted converter-voltage source converter hybrid high voltage direct current system
    Lei, Shunguang
    Shu, Hongchun
    Li, Zhimin
    Hu, Yinan
    Tian, Xincui
    Liu, Taiwen
    HIGH VOLTAGE, 2024, 9 (05) : 1159 - 1170
  • [9] Non-unit protection for long-distance LCC-HVDC transmission lines based on waveform characteristics of voltage travelling waves
    Liu, Zhen
    Gao, Houlei
    Luo, Sibei
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2023, 150
  • [10] Research on influencing factors of emergency power support for voltage source converter-based multi-terminal high-voltage direct current transmission system
    Li, Congshan
    Zhen, Zikai
    Sheng, Tingyu
    Liu, Yan
    Zhong, Pu
    Zhang, Xiaowei
    ARCHIVES OF ELECTRICAL ENGINEERING, 2022, 71 (04) : 881 - 894