Performance evaluation of CO2-based ventilation control to reduce CO2 concentration and condensation risk in residential buildings

被引:38
作者
Shin, Mi-Su [1 ]
Rhee, Kyu-Nam [2 ]
Lee, Eun-Tack [3 ]
Jung, Gun-Joo [2 ]
机构
[1] Seoul Natl Univ, Coll Engn, Dept Architecture, 1 Kwanak Ro, Seoul 08826, South Korea
[2] Pukyong Natl Univ, Coll Engn, Dept Architectural Engn, 45 Yongso Ro, Busan 48513, South Korea
[3] Samsung C&T Corp, Construct & Engn Grp, ENG Ctr, 26 Sangil Ro 6gil, Seoul 05288, South Korea
关键词
CO2; concentration; Ventilation; Residential building; CO2-Based ventilation control; Condensation mitigation; DEMAND-CONTROLLED VENTILATION; INDOOR ENVIRONMENT QUALITY; AIR-QUALITY; RATES; SLEEP; BEDROOMS; OFFICE; SYSTEM; WINTER;
D O I
10.1016/j.buildenv.2018.06.042
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
As the airtightness of a building envelope gets higher to achieve energy efficiency, the necessity of appropriate ventilation for residential buildings is continually increasing. Many residential buildings are equipped with energy recovery ventilators (ERV) for energy-efficient ventilation; however, the ERVs are usually operated by occupants' manual control, which often leads to insufficient or unnecessary ventilation. Because it is difficult to operate an ERV during nighttime, when occupants cannot control the system, a residential building can suffer from poor indoor air quality and increasing condensation risks. Herein, a CO2-based ventilation control strategy was implemented in an existing ERV system for residential buildings. Considering that most ERV systems operate with a central control, the appropriate CO2 sensor location (or representative room) was investigated in a mockup residential building. Comparative experiments were conducted to evaluate the control performances in terms of indoor air quality (CO2 control performance) and fan energy consumption. Experimental results showed that a living-room-based control can maintain an overall CO2 concentration in the entire space at acceptable levels. It was also shown that a living-room-based control resulted in reduced ventilation energy if the CO2 dispersed through open bedroom doors. The CO2-based ventilation control was modified to mitigate the condensation risk while minimizing the possibility of fan noise or cold draught. Through mock-up experiments on a modified CO2-based ventilation control, it was shown that CO2 concentrations can be maintained at acceptable levels and condensation risks can be mitigated even when the outdoor temperature decreases to -15 degrees C.
引用
收藏
页码:451 / 463
页数:13
相关论文
共 47 条
[1]   Review of heat/energy recovery exchangers for use in ZEBs in cold climate countries [J].
Alonso, Maria Justo ;
Liu, Peng ;
Mathisen, Hans M. ;
Ge, Gaoming ;
Simonson, Carey .
BUILDING AND ENVIRONMENT, 2015, 84 :228-237
[2]  
ASHRAE, 2014, Measurement of energy, demand and water savings-Guidelines 14
[3]  
ASHRAE, 2016, 6212016 ASHRAE, P40
[4]  
ASHRAE, 2016, 621 ASHRAE, P146
[5]   Ventilation rates in the bedrooms of 500 Danish children [J].
Beko, Gabriel ;
Lund, Toste ;
Nors, Fredrik ;
Toftum, Jorn ;
Clausen, Geo .
BUILDING AND ENVIRONMENT, 2010, 45 (10) :2289-2295
[6]   Modeling ventilation rates in bedrooms based on building characteristics and occupant behavior [J].
Bekoe, Gabriel ;
Toftum, Jorn ;
Clausen, Geo .
BUILDING AND ENVIRONMENT, 2011, 46 (11) :2230-2237
[7]   On the oversupply of heat to bedrooms during winter in highly insulated dwellings with heat recovery ventilation [J].
Berge, Magnar ;
Georges, Laurent ;
Mathisen, Hans Martin .
BUILDING AND ENVIRONMENT, 2016, 106 :389-401
[8]   A review of the environmental parameters necessary for an optimal sleep environment [J].
Caddick, Zachary A. ;
Gregory, Kevin ;
Arsintescu, Lucia ;
Flynn-Evans, Erin E. .
BUILDING AND ENVIRONMENT, 2018, 132 :11-20
[9]   Is CO2 a good proxy for indoor air quality in classrooms? Part 1: The interrelationships between thermal conditions, CO2 levels, ventilation rates and selected indoor pollutants [J].
Chatzidiakou, Lia ;
Mumovic, Dejan ;
Summerfield, Alex .
BUILDING SERVICES ENGINEERING RESEARCH & TECHNOLOGY, 2015, 36 (02) :129-161
[10]   Energy-efficient ventilation with air-cleaning mode and demand control in a multi-residential building [J].
Cho, Wanghee ;
Song, Doosam ;
Hwang, Seokho ;
Yun, Sungmin .
ENERGY AND BUILDINGS, 2015, 90 :6-14