Experimental study of an R1234ze(E)/R134a mixture (R450A) as R134a replacement

被引:73
作者
Mota-Babiloni, Adrian [1 ,2 ]
Navarro-Esbri, Joaquin [2 ]
Barragan-Cervera, Angel [2 ]
Moles, Francisco [2 ]
Peris, Bernardo [2 ]
机构
[1] Univ Politecn Valencia, Inst Ind Radiophys & Environm Safety, E-46022 Valencia, Spain
[2] Univ Jaume 1, Dept Mech Engn & Construct, ISTENER Res Grp, E-12071 Castellon de La Plana, Spain
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 2015年 / 51卷
关键词
Refrigeration; R450A; R134a; Mixture; Energy efficiency; Drop-in; 2,3,3,3-TETRAFLUOROPROP-1-ENE R1234YF; FLAMMABILITY LIMITS; BINARY-MIXTURES; PERFORMANCE; REFRIGERANTS; EQUILIBRIUM; R-1234ZE(E);
D O I
10.1016/j.ijrefrig.2014.12.010
中图分类号
O414.1 [热力学];
学科分类号
摘要
This work presents an experimental analysis of a non-flammable R1234ze(E)/R134a mixture (R450A) as R134a drop-in replacement. While R134a has a high GWP value (1430), the R450A GWP is only 547. The experimental tests are carried out in a vapour compression plant equipped with a variable-speed compressor. The replacement suitability has been studied combining different operating conditions: evaporation temperature, condensation temperature and the use of an internal heat exchanger (IHX). The drop-in cooling capacity of R450A compared with R134a is 6% lower as average. R450A COP is even higher to those resulting with R134a (approximately 1%). The discharge temperature of R450A is lower than that of R134a, 2K as average. The IHX has a similar positive influence on the energy performance of both fluids. In conclusion, R450A can be considered as a good candidate to replace R134a. (C) 2014 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:52 / 58
页数:7
相关论文
共 28 条
  • [2] [Anonymous], 1997, PHYS CHEMESTRY EMGIN, DOI DOI 10.1121/1.418074
  • [3] [Anonymous], VDA ALT REFR WINT M
  • [4] The next generation of refrigerants - Historical review, considerations, and outlook
    Calm, James M.
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION, 2008, 31 (07) : 1123 - 1133
  • [5] Measurements of isothermal (vapour plus liquid) equilibria data for {1,1,2,2-Tetrafluoroethane (R134) + trans-1,3,3,3-tetrafluoropropene (R1234ze (E))} at T = (258.150 to 288.150) K
    Dong, Xueqiang
    Guo, Hao
    Gong, Maoqiong
    Yang, Zhi
    Wu, Jianfeng
    [J]. JOURNAL OF CHEMICAL THERMODYNAMICS, 2013, 60 : 25 - 28
  • [6] Low GWP refrigerants R1234ze(E) and R1234ze(Z) for high temperature heat pumps
    Fukuda, Sho
    Kondou, Chieko
    Takata, Nobuo
    Koyama, Shigeru
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION, 2014, 40 : 161 - 173
  • [7] Flow pattern map, heat transfer and pressure drops during evaporation of R-1234ze(E) and R134a in a horizontal, circular smooth tube: Experiments and assessment of predictive methods
    Grauso, S.
    Mastrullo, R.
    Mauro, A. W.
    Thome, J. R.
    Vanoli, G. P.
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2013, 36 (02): : 478 - 491
  • [8] Honeywell, 2013, SOLST FAM HFOS
  • [9] Experimental study on condensation heat transfer and pressure drop in horizontal smooth tube for R1234ze(E), R32 and R410A
    Hossain, Md. Anowar
    Onaka, Yoji
    Miyara, Akio
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION, 2012, 35 (04) : 927 - 938
  • [10] Study on activated carbon/HFO-1234ze(E) based adsorption cooling cycle
    Jribi, Skander
    Saha, Bidyut Baran
    Koyama, Shigeru
    Chakraborty, Anutosh
    Ng, Kim Choon