Analysis and optimization of leakage impedance in a transformer with additional winding: A numerical and experimental study

被引:12
作者
Dawood, Kamran [1 ]
Isik, Fatih [2 ]
Komurgoz, Guven [1 ]
机构
[1] Istanbul Tech Univ, Dept Elect Engn, Istanbul, Turkey
[2] Astor Transformers, Ankara, Turkey
关键词
Finite element analysis; Leakage impedance; Leakage reactance; Magnetostatics analysis; Tap winding transformer; Tapping; POWER TRANSFORMER; REACTANCE; STRESS;
D O I
10.1016/j.aej.2022.05.014
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Transformers are one of the most important elements of electrical power systems. In several conditions, the same transformer is connected to many different networks with different voltage levels and the replacement of the transformer is one of the most difficult tasks for the power suppliers. Tap winding transformer can be used to overcome the problems of the variable primary or secondary voltages. However, tap winding positions and type significantly affect the overall leakage impedance and it is one of the major concerns for the tap winding transformer designers. In this paper, the tap winding transformer distance was optimized with additional tap winding on the high voltage winding side. To optimize and calculate the leakage impedance in the tap winding transformers with three different voltage levels, finite element analysis was used. The prototype tap winding transformer was manufactured with the help of the finite element method. The difference between the short-circuit experimental test and the finite element method result was less than 1%. The experimental results show that optimal calculation of the leakage impedance in the tap winding transformer can be achieved with help of the finite element analysis. (C) 2022 THE AUTHORS. Published by Elsevier BV on behalf of Faculty of Engineering, Alexandria University
引用
收藏
页码:11291 / 11300
页数:10
相关论文
共 20 条
  • [1] Short Circuit Stress Analysis Using FEM in Power Transformer on H-V Winding Displaced Vertically & Horizontally
    Ahmad, Ashfaq
    Javed, Iqra
    Nazar, Waseem
    Mukhtar, M. Asim
    [J]. ALEXANDRIA ENGINEERING JOURNAL, 2018, 57 (01) : 147 - 157
  • [2] Contribution to power transformers leakage reactance calculation using analytical approach
    Alves, Bruno S.
    Kuo-Peng, Patrick
    Dular, Patrick
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2019, 105 : 470 - 477
  • [3] Dawood K, 2020, INT CON ELECTR POWER, P75, DOI [10.1109/epecs48981.2020.9304948, 10.1109/EPECS48981.2020.9304948]
  • [4] Design optimisation for distance between additional and tap winding in high-voltage transformers
    Dawood, Kamran
    Koseoglu, Ahmet Kerem
    Komurgoz, Guven
    [J]. HIGH VOLTAGE, 2020, 5 (06) : 716 - 723
  • [5] Dawood K, 2019, J ELECTR SYST, V15, P213
  • [6] Del Vecchio R., 2017, TRANSFORMER DESIGN P
  • [7] Dongsheng H., 2021, INT J EMERG ELECTR P
  • [8] Grigsby L.L, 2017, ELECT POWER TRANSFOR, Vthird
  • [9] Electromechanical stress in transformers caused by inrush and short circuit currents
    Guimaraes, Ronaldo
    Delaiba, Antonio C.
    Rosentino, Arnaldo J. P., Jr.
    Saraiva, Elise
    de Oliveira, Jose C.
    [J]. JOURNAL OF THE BRAZILIAN SOCIETY OF MECHANICAL SCIENCES AND ENGINEERING, 2015, 37 (01) : 243 - 253
  • [10] An Approach to Power Transformer Asset Management Using Health Index
    Jahromi, Ali Naderian
    Piercy, Ray
    Cress, Stephen
    Service, Jim R. R.
    Fan, Wang
    [J]. IEEE ELECTRICAL INSULATION MAGAZINE, 2009, 25 (02) : 20 - 34