Mitigation of Multimodal SSR Using SEDC in the Shangdu Series-Compensated Power System

被引:50
作者
Xie, Xiaorong [1 ]
Guo, Xijiu [2 ]
Han, Yingduo [1 ]
机构
[1] Tsinghua Univ, State Key Lab Power Syst, Dept Elect Engn, Beijing 100084, Peoples R China
[2] No United Power Corp, Hohhot 010020, Inner Mongolia, Peoples R China
关键词
Field test; fixed series capacitor; subsynchronous resonance; supplementary excitation damping control (SEDC); STATIC VAR COMPENSATORS; STABILIZER;
D O I
10.1109/TPWRS.2010.2047280
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The Shangdu power plant has four 600-MW turbine-generators connected to the North-China Grid through two 500-kV transmissions, which are compensated with 45% fixed series capacitors. Extensive studies conducted on the system model indicate that the system suffers from multimodal subsynchronous resonance (SSR). To solve the problem, a countermeasure is developed by combining the supplementary excitation damping control (SEDC) and the torsional stress relay (TSR). In this paper, the characteristics of the SSR problem are investigated. Then the developed SEDC is presented. To validate the effectiveness of the proposed SEDC as well as the results of model studies, field tests were conducted under various operating conditions. The tests fully exposed the realistic threat of SSR in the system. Meanwhile, it is demonstrated that the developed SEDC can improve torsional damping significantly, and thus solve the multimodal SSR problem effectively. This is the first time in China that practical SEDCs have been developed and their ability to mitigate multimodal SSR has been verified in a real series-compensated system.
引用
收藏
页码:384 / 391
页数:8
相关论文
共 14 条
  • [1] Coprime factorisation approach in designing multi-input stabiliser for damping electromechanical oscillations in power systems
    Anaparthi, KK
    Pal, BC
    El-Zobaidi, H
    [J]. IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2005, 152 (03) : 301 - 308
  • [2] ON THE DEFINITION OF REACTIVE POWER UNDER NON-SINUSOIDAL CONDITIONS
    KUSTERS, NL
    MOORE, WJM
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1980, 99 (05): : 1845 - 1854
  • [3] OPERATION AND TEST OF NAVAJO SSR PROTECTIVE EQUIPMENT
    BOWLER, CEJ
    BAKER, DH
    MINCER, NA
    VANDIVEER, PR
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1978, 97 (04): : 1030 - 1035
  • [4] NAVAJO PROJECT REPORT ON SUBSYNCHRONOUS RESONANCE ANALYSIS AND SOLUTIONS
    FARMER, RG
    SCHWALB, AL
    KATZ, E
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1977, 96 (04): : 1226 - 1232
  • [5] HARB AM, 2003, P 2003 IEEE BOL POW, V3, P1
  • [6] HSU YY, 1995, P I ELECT ENG GEN TR, V142, P415
  • [7] DYNAMIC STABILIZER ONLINE EXPERIENCE
    KIMMEL, DS
    CARTER, MP
    BEDNAREK, JH
    JONES, WH
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1984, 103 (01): : 72 - 75
  • [8] A NEW POLE-PLACEMENT METHOD FOR EXCITATION CONTROL DESIGN TO DAMP SSR OF A NONIDENTICAL 2-MACHINE SYSTEM
    LI, QH
    ZHAO, DZ
    YU, YN
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 1989, 4 (03) : 1176 - 1181
  • [9] DAMPING OF TORSIONAL OSCILLATIONS USING EXCITATION CONTROL OF SYNCHRONOUS GENERATOR - THE IEEE 2ND BENCHMARK MODEL INVESTIGATION
    LI, W
    [J]. IEEE TRANSACTIONS ON ENERGY CONVERSION, 1991, 6 (01) : 47 - 54
  • [10] DYNAMIC STABILIZER VERIFICATION TESTS AT THE SAN-JUAN STATION
    RAMEY, DG
    KIMMEL, DS
    DORNEY, JW
    KROENING, FH
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1981, 100 (12): : 5011 - 5019