Coupling Characteristics of Electromagnetic Disturbance of On-Site Electronic Device Power Port in Substations and Its Suppression

被引:6
作者
Ge, Siqiao [1 ]
Liu, Weidong [1 ]
Li, Xing [1 ]
Ding, Dengwei [2 ]
机构
[1] Tsinghua Univ, Dept Elect Engn, State Key Lab Control & Simulat Power Syst & Gene, Beijing 100084, Peoples R China
[2] Tsinghua Univ, Sichuan Energy Internet Res Inst, Chengdu 610213, Peoples R China
基金
中国国家自然科学基金;
关键词
Substations; Couplings; Voltage measurement; Power supplies; Gas insulation; Switches; Power measurement; Electromagnetic compatibility (EMC); electromagnetic (EM) disturbance; on-site electronic device; power supply; switching operation; very fast transients (VFTs); GAS-INSULATED SUBSTATIONS; GROUND POTENTIAL RISE; TRANSIENT VOLTAGE; VFTO; DISCONNECTOR;
D O I
10.1109/TEMC.2021.3064154
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The switching operations of circuit breakers and disconnectors in substations can generate very fast transients, including transient earth voltage rise and intense electromagnetic radiation, causing severe disturbance of on-site electronic devices in substations and seriously affecting the development of smart power equipment. The power supply of an on-site electronic device provides a path along which the disturbance couples with the device. In this article, we investigated the coupling mechanism and measures to suppress this disturbance. We found that, for most on-site electronic devices, their power supply includes a power line that connects the exterior and interior of the shielding box, greatly reducing the shielding effectiveness and inducing disturbance from the outside to the inside. This article proposes a shielding-crossing isolation transformer as the power supply of which the primary winding is outside and the secondary winding is inside of the shielding box, without a power line across the shielding box. This arrangement proved to deliver the high performance in terms of eliminating disturbance from the power supply. This article provides an understanding of the mechanism according to which the electromagnetic disturbance couples through the power supply. A method to determine the electromagnetic compatibility of on-site electronic devices in a substation is also proposed.
引用
收藏
页码:1584 / 1592
页数:9
相关论文
共 33 条
  • [1] [Anonymous], 2001, 6100065 IEC
  • [2] A Time-Domain Method for the Horizontal Electric Field Calculation at the Surface of Two-Layer Earth Due to Lightning
    Barbosa, Celio Fonseca
    Saldanha Paulino, Jose Osvaldo
    Boaventura, Wallace do Couto
    [J]. IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2013, 55 (02) : 371 - 377
  • [3] Bin Liu, 2014, 2014 International Conference on Power System Technology (POWERCON 2014), P1828, DOI 10.1109/POWERCON.2014.6993662
  • [4] New Methods of Damping Very Fast Transient Overvoltages in Gas-Insulated Switchgear
    Burow, Simon
    Straumann, Ueli
    Koehler, Wolfgang
    Tenbohlen, Stefan
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2014, 29 (05) : 2332 - 2339
  • [5] Study of Transient Enclosure Voltage Coupling to Secondary Cables in a Gas-Insulated Substation
    Cai, Yuanji
    Guan, Yonggang
    Liu, Weidong
    He, Jiaxi
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (02) : 761 - 768
  • [6] Statistical characteristics of transient enclosure voltage in ultra-high-voltage gas-insulated switchgear
    Cai, Yuanji
    Guan, Yonggang
    Liu, Weidong
    [J]. PLASMA SCIENCE & TECHNOLOGY, 2017, 19 (06)
  • [7] Cai YJ, 2015, IEEE IMTC P, P115, DOI 10.1109/I2MTC.2015.7151250
  • [8] Influence of the Ground Potential Rise on the Residual Voltage of Low-Voltage Surge Protective Devices due to Nearby Lightning Flashes
    Chen, Shaodong
    Zhang, Yijun
    Chen, Chang
    Yan, Xu
    Lu, Weitao
    Zhang, Yang
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2016, 31 (02) : 596 - 604
  • [9] Cheng L, 2018, 2018 2ND IEEE CONFERENCE ON ENERGY INTERNET AND ENERGY SYSTEM INTEGRATION (EI2)
  • [10] CIGREWorking Group, 1997, GUID EMC POW PLANTS