Faulty Line Selection Method Based on Comprehensive Dynamic Time Warping Distance in a Flexible Grounding System

被引:13
|
作者
He, Yu [1 ]
Zhang, Xinhui [1 ]
Wu, Wenhao [1 ]
Zhang, Jun [1 ]
Bai, Wenyuan [1 ]
Guo, Aiyu [1 ]
Chen, Yu [1 ]
机构
[1] Shandong Univ Technol, Sch Elect & Elect Engn, Zibo 255000, Peoples R China
关键词
flexible grounding system; faulty line selection; single-phase grounding fault; Comprehensive Dynamic Time Warping (CDTW) distance; transient projection method;
D O I
10.3390/en15020471
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
A flexible grounding system is a system in which the neutral point of the power supply is grounded via the arc suppression coil in parallel with a low-resistance resistor. When operating normally or a temporary ground fault occurs, the arc suppression coil is used for grounding, whereas the small resistance is switched on when a permanent ground fault occurs. At present, the problem of low protection sensitivity when a high-resistance ground fault occurs in a flexible grounding system has not been solved yet. According to the characteristics of low waveform similarity between the faulty line and the non-faulty line when a single-phase grounding fault occurred, a new faulty line selection method based on a combination of Dynamic Time Warping (DTW) distance and the transient projection method is proposed in this paper. Firstly, the fault transient signal is extracted by a digital filter as a basis for faulty line selection. Secondly, the transient zero-sequence current of each line is projected onto the busbar transient zero-sequence voltage, and the projected DTW distance of each line is calculated. Finally, according to the calculation formula of waveform comprehensive similarity coefficient, the Comprehensive DTW (CDTW) distance is obtained, and the top three CDTW distance values are selected to determine the faulty line. If the maximum value is greater than the sum of the other two CDTW distance values, the line corresponding to the maximum value is judged as the faulty line; otherwise, it is judged as a busbar fault. The simulation results based on MATLAB/Simulink and field data test show that the method can accurately determine the faulty line under diverse fault conditions.
引用
收藏
页数:16
相关论文
共 50 条
  • [21] An Adaptive Fault Line Selection Method Based on Wavelet Packet Comprehensive Singular Value for Small Current Grounding System
    Wei, Xiangxiang
    Yang, Dechang
    2015 5TH INTERNATIONAL CONFERENCE ON ELECTRIC UTILITY DEREGULATION AND RESTRUCTURING AND POWER TECHNOLOGIES (DRPT 2015), 2015, : 1110 - 1114
  • [22] Faulty section location method for high impedance grounding fault in resonant grounding system based on discrete Fre<acute accent>chet distance
    Xu, Honglu
    Zhang, Xinhui
    Sun, Haoyue
    Wu, Wenhao
    Zhu, Jiaxi
    Wang, Fuqian
    ELECTRIC POWER SYSTEMS RESEARCH, 2025, 238
  • [23] Faulty Line Selection Method for Distribution Network Based on Variable Scale Bistable System
    Wang, Xiaowei
    Gao, Jie
    Song, Guobing
    Cheng, Qiming
    Wei, Xiangxiang
    Wei, Yanfang
    JOURNAL OF SENSORS, 2016, 2016
  • [24] High Impedance Fault Line Selection Method Based on Inner Product Projection of Different Time Periods for Flexible Grounding Systems
    Wang X.
    Liu W.
    Guo L.
    Liang Z.
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2024, 39 (01): : 154 - 167
  • [25] Dynamic time warping–based feature selection method for foot gesture cobot operation mode selection
    Gilde Vanel Tchane Djogdom
    Martin J.-D. Otis
    Ramy Meziane
    The International Journal of Advanced Manufacturing Technology, 2023, 126 : 4521 - 4541
  • [26] A Novel Fault Line Selection Method of Resonant Grounding System
    Yuan, Yongjun
    Chen, Xiaogang
    Yang, Lei
    Zeng, Xiangjun
    Cai, Jun
    Yu, Minqi
    2017 IEEE CONFERENCE ON ENERGY INTERNET AND ENERGY SYSTEM INTEGRATION (EI2), 2017,
  • [27] New method for transient line selection in distribution system based on grounding fault transferred
    Li, Yilin
    Yin, Xianggen
    Chen, Rui
    JOURNAL OF ENGINEERING-JOE, 2019, (16): : 2822 - 2826
  • [28] A Fault Line Selection Method for Small Current Grounding System Based on Big Data
    Shao, Zheng
    Wang, Liancheng
    Zhang, Han
    2016 IEEE PES ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2016, : 2470 - 2474
  • [29] Fault Line Selection Method for Small Current Grounding System Based on Improved GoogLeNet
    Hao S.
    Zhang X.
    Ma R.
    Wen H.
    Ma X.
    An B.
    Li J.
    Dianwang Jishu/Power System Technology, 2022, 46 (01): : 361 - 368
  • [30] The fault line selection method of small current grounding system based on wavelet transformation
    Li, Hua
    Li, Lingling
    Huang, Shanshan
    Li, Fengqiang
    PROGRESS IN POWER AND ELECTRICAL ENGINEERING, PTS 1 AND 2, 2012, 354-355 : 149 - 152