共 50 条
Modeling of energy performance of a house with three configurations of building-integrated photovoltaic/thermal systems
被引:89
|作者:
Pantic, S.
[1
]
Candanedo, L.
[1
]
Athienitis, A. K.
[1
]
机构:
[1] Concordia Univ, Dept Bldg Civil & Environm Engn, Montreal, PQ H3G 2W1, Canada
基金:
加拿大自然科学与工程研究理事会;
关键词:
Building-integrated photovoltaic/thermal system;
Thermal storage;
Energy performance;
D O I:
10.1016/j.enbuild.2010.05.014
中图分类号:
TU [建筑科学];
学科分类号:
0813 ;
摘要:
A theoretical and experimental study of energy performance of three different open loop air heating building-integrated photovoltaic/thermal (BIPV/T) systems that utilize recovered heat for home heating is presented. The configurations are: Configuration 1: base case of unglazed BIPV with airflow under it; Configuration 2: addition of 1.5 m vertical glazed solar air collector in series with Configuration 1; Configuration 3: addition of a glazing over the PV. The model developed has been verified against experimental data from a solar research house for Configuration 1. Obtained relationships for BIPV/T system exiting air temperature as function of solar irradiance and air speed in PV cavity may be used for developing fan airflow control strategies to achieve desired outlet air temperature suitable for different applications. For Configuration 1, preheated air is suitable for HVAC system and domestic hot water (DHW) preheating. Higher outlet air temperatures of the PV cavity suitable for DHW might be achieved by utilizing Configurations 2 or 3. With Configuration 2, significant outlet air temperatures are achieved in winter along with enhanced thermal efficiency making it suitable for coupling with a rockbed heat storage. Finally, Configuration 3 significantly reduces electricity production and may lead to excessively high PV panel temperatures. (C) 2010 Elsevier B.V. All rights reserved.
引用
收藏
页码:1779 / 1789
页数:11
相关论文