Excitation system protective limiters and their effect on volt/var control - Design, computer modeling, and field testing

被引:23
作者
Murdoch, A [1 ]
Delmerico, RW
Venkataraman, S
Lawson, RA
Curran, JE
Pearson, WR
机构
[1] GE, Power Syst Energy Consulting, Schenectady, NY 12301 USA
[2] GE, Dr Syst, Salem, VA USA
关键词
excitation controls; generator controls; protective limiters; system stability; voltage stability;
D O I
10.1109/60.900506
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The action of excitation system protective limiters and var regulation are often not taken into account in planning studies, and actual units may be quite different than simulations. This may lead to incorrect predictions of actual stability limitations, or even voltage collapse phenomena, The design of the excitation system protective limiters such as Over Excitation Limiters (OEL), Under Excitation Limiters (UEL) and Volts/Hertz (V/Hz) is explained, and models presented, For system events where these controls and limiters may become active, modeling in transient stability studies is important to correctly predict volt/var performance. Specific models applicable to the GE EX2000 digital-based control systems are shown for reference, although the general concepts discussed here are applicable to any other excitation equipment, An important aspect of the new digital-based excitation controls is that they allow for more intelligent limiter functions and protective features not convenient with older equipment, Test procedures and results are shown to illustrate the limiter performance.
引用
收藏
页码:440 / 450
页数:11
相关论文
共 18 条
[1]  
ADAMS CG, 1948, AIEE T, V67, P521
[2]  
[Anonymous], 1995, IEEE TASK FORCE EXCI, P524
[3]  
[Anonymous], 1995, IEEE TASK FORCE EXCI, P706
[4]  
[Anonymous], 42151992 IEEE
[5]  
[Anonymous], 1996, DIGITAL EXCITATION S, V11, P607
[6]  
BERDY J, 1972, 1105 CIGRE
[7]   A UTILITY PERSPECTIVE ON UNDER-EXCITATION LIMITERS [J].
BERUBE, GR ;
HAJAGOS, LM ;
BEAULIEU, RE .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 1995, 10 (03) :532-537
[8]   PERFORMANCE OF EXCITATION SYSTEMS UNDER ABNORMAL CONDITIONS [J].
BOBO, PO ;
SKOOGLUN.JW ;
WAGNER, CL .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1968, PA87 (02) :547-&
[9]   STEADY-STATE STABILITY OF A REMOTE GAS-TURBINE GENERATING-STATION - FIELD-TESTS AND VALIDATION OF COMPUTER-SIMULATION RESULTS [J].
CHOI, SS ;
LARKIN, R .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1993, 8 (04) :1518-1524
[10]   IMPACT OF UNDER-EXCITATION LIMIT CONTROL ON POWER-SYSTEM DYNAMIC PERFORMANCE [J].
DEOLIVEIRA, SEM ;
DOSSANTOS, MG .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1995, 10 (04) :1863-1869