Research on Partial Discharge Characteristics of Protrusion defect in GIS Under Oscillating Lightning Impulse Voltage

被引:0
作者
Hu, Mengchen [1 ]
Han, Xutao [2 ]
Li, Qiuyang [1 ]
Wang, Shengfu [1 ]
Chen, Yao [1 ]
Li Junhao [2 ]
机构
[1] State Grid Qinghai Elect Power Res Inst, Xining, Peoples R China
[2] Xi An Jiao Tong Univ, State Key Lab Elect Insulat & Power Equipment, Xian, Peoples R China
来源
2016 INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (CMD) | 2016年
关键词
GIS; oscillating impulse voltage; protrusion; partial discharge;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In order to ensure the safe operation of the gas insulated switchgear (GIS), on-site impulse withstand voltage test is becoming more and more important. Oscillating impulse voltage is very suitable for the field test due to its high generating efficiency. By detecting the partial discharge when conducting on-site impulse withstand voltage test, the insulation state of GIS can be overall known. The protrusion is a typical and harmful defect in GIS, so it is very significant to research the partial discharge characteristics of protrusion in GIS under oscillating lightning impulse voltage. In this paper, we applied oscillating lightning impulse voltage on a 330kV GIS which was set a protrusion at the conductor and we measured the partial discharge by the inner UHF sensor at the same time. We analyze the variation of discharge position, maximum discharge amplitude and discharge number with the increasing of voltage and compare the results of different frequencies voltage. Our studies show that the partial discharges mainly occur at the peak of the oscillating lightning impulse voltage. With the increasing of the voltage amplitude, the maximum discharge amplitude and discharge number also increase. And with the increasing of the voltage frequency, the partial discharge inception voltage increases. The results of this paper are helpful for the on-site impulse withstand voltage test.
引用
收藏
页码:920 / 923
页数:4
相关论文
共 10 条
[1]  
[Anonymous], 2010, IEC600603
[2]  
Boeck W., 1998, Electra, V176, P67
[3]   Features Extraction and Mechanism Analysis of Partial Discharge Development under Protrusion Defect [J].
Dong, Yu-lin ;
Tang, Ju ;
Zeng, Fu-ping ;
Liu, Min .
JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY, 2015, 10 (01) :344-354
[4]  
Gao WS, 2013, IEEE T DIELECT EL IN, V20, P782
[5]   Partial Discharge Characteristics over SF6/Epoxy Interfaces under Impulse Voltage [J].
Li, Junhao ;
Zhang, Liang ;
Liang, Jianfeng ;
Yao, Xiu ;
Li, Yanming .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2013, 20 (06) :2158-2164
[6]   GIS insulation co-ordination: On-site tests and dielectric diagnostic techniques, a utility point of view [J].
Sabot, A ;
Petit, A ;
Taillebois, JP .
IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (03) :1309-1316
[7]   UHF Technique for Identification of Partial Discharge in a Composite Insulation Under AC and DC voltages [J].
Sarathi, R. ;
Koperundevi, G. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2008, 15 (06) :1724-1730
[8]  
Shu W, 2005, 2005 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, P83
[9]   Feature extraction and severity assessment of partial discharge under protrusion defect based on fuzzy comprehensive evaluation [J].
Zeng, Fuping ;
Dong, Yulin ;
Tang, Ju .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2015, 9 (16) :2493-2500
[10]   Characteristics and Development Mechanisms of Partial Discharge in SF6 Gas Under Impulse Voltages [J].
Zhao, Xuefeng ;
Yao, Xiu ;
Guo, Zhifeng ;
Li, Junhao ;
Si, Wenrong ;
Li, Yanming .
IEEE TRANSACTIONS ON PLASMA SCIENCE, 2011, 39 (02) :668-674