Simplified Model of Contaminant Dispersion in Rooms Conditioned by Chilled-Ceiling Displacement Ventilation System

被引:22
|
作者
Kanaan, M. [1 ]
Ghaddar, N. [1 ]
Ghali, K. [1 ]
机构
[1] Amer Univ Beirut, Lebanon, NH USA
来源
HVAC&R RESEARCH | 2010年 / 16卷 / 06期
关键词
AIR-DISTRIBUTION SYSTEMS; DESIGN;
D O I
10.1080/10789669.2010.10390933
中图分类号
O414.1 [热力学];
学科分类号
摘要
The aim of this paper is to develop and experimentally validate a simplified model to predict carbon dioxide transport and distribution in rooms conditioned by chilled-ceiling displacement ventilation (COD system for known supply thermal and flow conditions and chilled-ceiling temperature. The transport model of carbon dioxide considers upward convective flow by the rising thermal wall and source plumes, the CO2 lateral diffusion into plume-adjacent air layers, and vertical CO2 diffusion in air inside and outside the plumes. Experiments were performed for different supply air CO2 concentrations, supply air flow rates, and strengths of heat sources. Experimental measurements of the vertical profile of air temperature, and carbon dioxide concentration compared well with values calculated by the model. The indoor air quality is assessed based on levels of carbon dioxide concentration in the radiant- cooled space. The model can be put to practical use in finding the maximum acceptable fraction of return air to be mixed with the supply while the air quality in the breathing zone remains acceptable.
引用
收藏
页码:765 / 783
页数:19
相关论文
共 50 条
  • [41] Cascaded liquid desiccant system for humidity control in space conditioned by cooled membrane ceiling and displacement ventilation
    Charara, Jinane
    Ghaddar, Nesreen
    Ghali, Kamel
    Zoughaib, Assaad
    Simonetti, Marco
    ENERGY CONVERSION AND MANAGEMENT, 2019, 195 : 1212 - 1226
  • [42] A dynamic simplified model of radiant ceiling cooling integrated with underfloor ventilation system
    Zhang, Dongliang
    Xia, Xueying
    Cai, Ning
    APPLIED THERMAL ENGINEERING, 2016, 106 : 415 - 422
  • [43] New airborne pathogen transport model for upper-room UVGI spaces conditioned by chilled ceiling and mixed displacement ventilation: Enhancing air quality and energy performance
    Kanaan, Mohamad
    Ghaddar, Nesreen
    Ghali, Kamel
    Araj, Georges
    ENERGY CONVERSION AND MANAGEMENT, 2014, 85 : 50 - 61
  • [44] Numerical investigation of airborne transmission in low-ceiling rooms under displacement ventilation
    Wang, Changchang
    Hong, Jiarong
    PHYSICS OF FLUIDS, 2023, 35 (02)
  • [45] Investigation of the displacement effect of a diffuse ceiling ventilation system
    Petersen, Steffen
    Christensen, Niels Uhre
    Heinsen, Caroline
    Hansen, Anne Sophie
    ENERGY AND BUILDINGS, 2014, 85 : 265 - 274
  • [46] A simplified mathematical model for predicting cross contamination in displacement ventilation air-conditioned spaces
    Habchi, Carine
    Ghali, Kamel
    Ghaddar, Nesreen
    JOURNAL OF AEROSOL SCIENCE, 2014, 76 : 72 - 86
  • [47] Thermal comfort in chilled ceiling and displacement ventilation environments: Vertical radiant temperature asymmetry effects
    Hodder, SG
    Loveday, DL
    Parsons, KC
    Taki, AH
    ENERGY AND BUILDINGS, 1998, 27 (02) : 167 - 173
  • [48] Combining chilled ceiling, displacement ventilation and desiccant dehumidification for indoor air quality and thermal comfort
    Hao, XL
    Zhang, GQ
    Chen, YM
    Zou, SH
    INDOOR AIR 2005: PROCEEDINGS OF THE 10TH INTERNATIONAL CONFERENCE ON INDOOR AIR QUALITY AND CLIMATE, VOLS 1-5, 2005, : 1248 - 1253
  • [49] Investigation on indoor airflow and contaminant dispersion of diffuse ceiling ventilation in heating and cooling modes
    Peng, Pei
    Zhang, Chen
    Li, Wenqiang
    Pomianowski, Michal
    Gong, Guangcai
    Fang, Xi
    Chun, Liang
    Guo, Rui
    JOURNAL OF BUILDING ENGINEERING, 2023, 80
  • [50] A simplified combined displacement and personalized ventilation model
    Alain, Makhoul
    Kamel, Ghali
    Nesreen, Ghaddar
    HVAC&R RESEARCH, 2012, 18 (04): : 737 - 749