Correlation between space charge distribution and water-tree location in aged XLPE cable

被引:23
|
作者
Suzuki, K [1 ]
Tanaka, Y
Takada, T
Ohki, Y
Takeya, C
机构
[1] Musashi Inst Technol, Tokyo 158, Japan
[2] Waseda Univ, Tokyo 160, Japan
[3] Tatsuta Elect Wire & Cable Co Ltd, Osaka, Japan
关键词
D O I
10.1109/94.910428
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The correlation between charge distribution in an aged crosslinked polyethylene (XLPE) cable and the location of water trees has been studied. The space charge radial distributions at different angle in the insulating wall of a service-aged XLPE coaxial cable, induced by application of a de stress, were measured using the pulsed electroacoustic (PEA) method. Furthermore, a cross section of sliced insulating wall was observed with an optical microscope to compare with the radial space charge distribution. The cable under investigation was electrically aged in service at 6.6 kV ac for 25 years in wet conditions. Water trees were found at the position in which space charge was observed. On the other hand, no water tree was found at the position in which the space charge was not observed. Judging from these results, the space charge measurement seems to be useful for the diagnosis of water trees in aged cables.
引用
收藏
页码:78 / 81
页数:4
相关论文
共 50 条
  • [1] Behavior of Residual Charges in Water-tree Degraded XLPE Sheets and Cable
    Ebinuma, Yasumitsu
    Masui, Noriaki
    TRANSACTIONS ON ELECTRICAL AND ELECTRONIC MATERIALS, 2006, 7 (05) : 224 - 229
  • [2] Investigation on Space Charge Behavior in Water Tree Aged Crosslinked Polyethylene (XLPE) Cable by Experiment and Simulation
    Zhang, Yu
    Liu, Deyuan
    Wu, Jiandong
    Yin, Yi
    2017 INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATING MATERIALS (ISEIM), VOLS 1 & 2, 2017, : 613 - 616
  • [4] Correlation between the AC breakdown strength and spacecharge distribution of water tree aged XLPE
    Lee, JH
    Cho, SM
    Song, IK
    1998 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, VOLS 1 AND 2, 1998, : 657 - 660
  • [5] Power frequency breakdown characteristics of water-tree retardant XLPE power cable
    Yan, Meng-Kun
    Luo, Jun-Hua
    Yang, Li-Ming
    Zheng, Chuan-Bao
    Gaodianya Jishu/High Voltage Engineering, 2009, 35 (10): : 2395 - 2400
  • [6] Study on Charge Dynamics in Water-Tree XLPE Insulation for Deterioration Diagnosis
    Ra, Nhet
    Futami, Hiroyuki
    Kawashima, Tomohiro
    Murakami, Yoshinobu
    Hozumi, Naohiro
    Kurihara, Takashi
    Okamoto, Tatsuki
    2017 INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATING MATERIALS (ISEIM), VOLS 1 & 2, 2017, : 343 - 346
  • [7] Space charge analysis of electrotherinally aged XLPE cable insulation
    Lanca, M. C.
    Fu, M.
    Neagu, E.
    Dissado, L. A.
    Marat-MendeS, J.
    Tzimas, A.
    Zadeh, S.
    JOURNAL OF NON-CRYSTALLINE SOLIDS, 2007, 353 (47-51) : 4462 - 4466
  • [8] Diagnosis and restoration of water tree aged XLPE cable materials
    Faremo, H
    Ildstad, E
    CONFERENCE RECORD OF THE 1996 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, VOLS 1 AND 2, 1996, : 596 - 599
  • [9] Influence of water-tree degradation on electroluminescence spectrum in XLPE
    Watanabe, M.
    Mito, T.
    Muramoto, Y.
    Shimizu, N.
    2006 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2006, : 720 - 723
  • [10] Space Charge Formation and Physicochemical Properties of Aged XLPE Cable Insulation
    Li, Shengtao
    Li, Weiwei
    Li, Jianying
    Wang, Xia
    Li, Huan
    Jing, Yu
    PROCEEDINGS OF 2012 IEEE INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (IEEE CMD 2012), 2012, : 408 - 411