Aging State Assessment of Transformer Oil Based on UV-Vis Spectrum and Fuzzy Algorithm

被引:1
作者
Feng, Dawei [1 ]
Yan, Xiaoyu [1 ]
Guo, Yixin [2 ]
机构
[1] Hebei Univ Technol, State Key Lab Reliabil & Intelligence Elect Equip, Tianjin, Peoples R China
[2] State Grid Int Dev Co Ltd, Beijing, Peoples R China
来源
2022 IEEE 21ST INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS (ICDL) | 2022年
关键词
insulation oil; aging state; UV-Vis spectrum; fuzzy algorithm;
D O I
10.1109/ICDL49583.2022.9830921
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Insulation oil is used as insulation and cooling medium in transformers. With the operation of the transformers, insulation oil gradually ages, leading to decline in insulation strength, blockage in oil channels, and difficulty in heat dissipation, which brings potential risks to the equipment and power system. Therefore, timely and accurate aging state assessment of insulation oil is significant to guide the timing of oil filtering or oil replacement. In this paper, the degradation laws of mineral oil and 3-element mixed insulation oil were studied through accelerated thermal aging tests, and the parameters indicating aging state of oil were measured. Test results showed that the characteristic value of UV-Vis (ultraviolet-visible) spectrum was closely related to the conventional aging parameters, such as acid value, interfacial tension, and resistivity. A mathematical model was established between the characteristic value and conventional aging parameters of insulation oil, which showed high accuracy verified by oil-replacement aging test. Finally, an aging state evaluation model of insulation oil was established with fuzzy algorithm based on the abovementioned mathematical model, which is expected to be used for online monitoring of oil aging state.
引用
收藏
页数:4
相关论文
共 12 条
[1]   Condition Assessment of Aged Transformer Oil Using Photoluminescence-Based Features [J].
Alshehawy, Abdelrahman M. ;
Mansour, Diaa-Eldin A. ;
Ghali, Mohsen .
PROCEEDINGS OF 2021 5TH INTERNATIONAL CONFERENCE ON CONDITION ASSESSMENT TECHNIQUES IN ELECTRICAL SYSTEMS (IEEE CATCON 2021), 2021, :282-285
[2]  
[Anonymous], 2008, 2008 IEEE INT C DIEL
[3]  
Bakar N. Abu, 2015, 2015 IEEE POWER ENER, P1
[4]   Aging of transformer insulating materials under selective conditions [J].
Fofana, I. ;
Borsi, H. ;
Gockenbach, E. ;
Farzaneh, M. .
EUROPEAN TRANSACTIONS ON ELECTRICAL POWER, 2007, 17 (05) :450-470
[5]   Assessing Insulating Oil Degradation by Means of Turbidity and UV/Vis Spectrophotometry Measurements [J].
Hadjadj, Y. ;
Fofana, I. ;
Sabau, John ;
Briosso, Eduardo .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2015, 22 (05) :2653-2660
[6]  
Hussain K, 2014, 2014 18 NATL POWER S, P1
[7]  
IEEE, 2013, IEEE Std C57.152-2013
[8]  
Kalathiripi H., 2017, P IEEE 19 INT C DIEL, P1
[9]  
Li Xiao-hu, 2006, Proceedings of the CSEE, V26, P95
[10]   Thermal and Electrical Properties of a Novel 3-Element Mixed Insulation Oil for Power Transformers [J].
Liao, Ruijin ;
Feng, Dawei ;
Hao, Jian ;
Yang, Lijun ;
Li, Jian ;
Wang, Qian ;
Zhang, Shiling .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2019, 26 (02) :610-617