Investigation of the performance of a high-temperature heat pump using parallel cycles with serial heating on the water side

被引:34
作者
Wang, Kai [1 ]
Cao, Feng [1 ]
Wang, Shouguo [1 ]
Xing, Ziwen [1 ]
机构
[1] Xi An Jiao Tong Univ, Sch Energy & Power Engn, Xian 710049, Peoples R China
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 2010年 / 33卷 / 06期
基金
中国国家自然科学基金;
关键词
Heat pump; Screw compressor; High temperature; Design; Oil injection Thermodynamic cycle; Calculation; Performance; Test-measurement; SYSTEM;
D O I
10.1016/j.ijrefrig.2010.04.016
中图分类号
O414.1 [热力学];
学科分类号
摘要
High-temperature heat pumps can be widely utilized for industrial heating as an energy-saving method due to their high condensing temperatures. This paper describes a cycle analysis and experimental study on the performance of a high-temperature heat pump (HTHP) system. The performance comparisons are conducted using performance calculations among the parallel cycles with serial heating on the water side, a two-stage compression cycle and a single-stage cycle. The results show that the performance of the heat pump using parallel cycles with serial heating is the best when the condensing temperature exceeds 75 degrees C. Based on the cycle analysis, a prototype HTHP using parallel cycles with serial heating on the water side with a heating capacity of 700 kW was built in this study. Also, a screw compressor was modified due to the high-temperature conditions. The measured performance shows that the HTHP can stably provide an outlet water temperature of up to 85 degrees C with a high coefficient of performance (COP). The experimental results indicate that the average heating capacity and coefficient of performance of the HTHP could be improved significantly in high-temperature conditions due to the parallel cycles with serial heating on the water side and the modified compressor. All the results indicate that the HTHP using parallel cycles and modified compressor with serial heating on the water side is very competitive in industrial heating applications. (C) 2010 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:1142 / 1151
页数:10
相关论文
共 15 条
[1]  
[Anonymous], 7 INT EN AG HEAT PUM
[2]   Two-stage air-source heat pump for residential heating and cooling applications in northern US climates [J].
Bertsch, Stefan S. ;
Groll, Eckhard A. .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2008, 31 (07) :1282-1292
[3]   The fluorinated olefin R-1234ze(Z) as a high-temperature heat pumping refrigerant [J].
Brown, J. Steven ;
Zilio, Claudio ;
Cavallini, Alberto .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2009, 32 (06) :1412-1422
[4]   Two-stage direct expansion solar-assisted heat pump for high temperature applications [J].
Chaturvedi, S. K. ;
Abdel-Salam, T. M. ;
Sreedharan, S. S. ;
Gorozabel, F. B. .
APPLIED THERMAL ENGINEERING, 2009, 29 (10) :2093-2099
[5]   THERMODYNAMIC SCREENING OF SOME HFCS AND HFES FOR HIGH-TEMPERATURE HEAT-PUMPS AS ALTERNATIVES TO CFC114 [J].
DEVOTTA, S ;
PENDYALA, VR .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1994, 17 (05) :338-342
[6]  
EES, 2006, EES ENG EQ SOLV
[7]   SELECTION OF WORKING FLUIDS FOR HIGH-TEMPERATURE HEAT-PUMPS [J].
GOKTUN, S .
ENERGY, 1995, 20 (07) :623-625
[8]   Heat pump system utilizing produced water in oil fields [J].
Gu, ZL ;
Qiu, J ;
Li, Y ;
Cai, GU .
APPLIED THERMAL ENGINEERING, 2003, 23 (15) :1959-1970
[9]  
Kline S.J., 1952, ASME Mechanical Engineering, V75, P3, DOI DOI 10.1016/J.CHAOS.2005.11.046
[10]   High temperature hot water heat pump with non-azeotropic refrigerant mixture HCFC-22/HCFC-141b [J].
Li, TX ;
Guo, KH ;
Wang, RZ .
ENERGY CONVERSION AND MANAGEMENT, 2002, 43 (15) :2033-2040