Influence of Different Types of Magnetic Shields on the Thermal Behavior and Ampacity of Underground Power Cables

被引:38
作者
del Pino Lopez, Juan Carlos [1 ]
Cruz Romero, Pedro [1 ]
机构
[1] Univ Seville, Dept Elect Engn, Seville 41092, Spain
关键词
Ampacity; magnetic-field shielding; H-layout; horizontal plate; reverse-U; underground cables;
D O I
10.1109/TPWRD.2011.2158593
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper analyzes the thermal effects derived from the use of different screen shapes when shielding the magnetic field generated by underground power cables. A parametric analysis is developed to show the influence of the geometrical and the electrical parameters of the shield on the maximum temperature achieved by the power cables in order to analyze the impact of this technique on the ampacity of the line. A 2-D finite element approach is employed in this study to verify the performance of different types of screens (horizontal plate, reverse-U, and H-layout) in terms of shielding efficiency, overheating of the power cables, and operational costs.
引用
收藏
页码:2659 / 2667
页数:9
相关论文
共 19 条
[1]  
Anders G.J., 1997, RATING ELECT POWER C
[2]  
[Anonymous], 2009, TB373 CIGRE WORK GRO
[3]  
[Anonymous], 2002, 6028711 IEC
[4]  
[Anonymous], 1997, 60287331 IEC
[5]  
[Anonymous], Eur. patent application EP, Patent No. 1598911
[6]  
[Anonymous], 2007, 6028721 IEC
[7]  
[Anonymous], 1998, COMS MULT
[8]  
Bottauscio O., 2004, IEEE T MAGN 2, V40
[9]   Evaluation of different analytical and semi-analytical methods for the design of ELF magnetic field shields [J].
Canova, A ;
Manzin, A ;
Tartaglia, M .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2002, 38 (03) :788-796
[10]  
D'Amore M., 2003, IEEE INT S EL COMP B