Analysis on Protection Coordination of OCRs Using Voltage Components for the Application of SFCL in a Power Distribution System with DG

被引:6
|
作者
Lim, Sung-Hun [1 ]
Park, Min-Ki [1 ]
机构
[1] Soongsil Univ, Dept Elect Engn, Seoul 06978, South Korea
基金
新加坡国家研究基金会;
关键词
Dispersed generation (DG); overcurrent relay (OCR); fault current; superconducting fault current limiter (SFCL); power distribution system; protection coordination; malfunction;
D O I
10.1109/TASC.2021.3066045
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
As the importance of renewable energy increases, the capacity of dispersed generations (DGs) has increased worldwide. However, the connection of DGs in the power distribution system can cause the fault current to increase as well as malfunction of the overcurrent relay (OCR) due to the reverse directional fault current. As the countermeasure to limit the fault current in the power distribution system with DG, though the superconducting fault current limiter (SFCL) is reported to be more effective, the research on the protection algorithm of the protective relay considering the application of SFCL is preferentially required. In this paper, the correction method of the OCR using voltage components for application of SFCL in a power distribution system with DG was suggested. To verify the effectiveness of the suggested method, the fault simulation for the power distribution system with DG including the OCR and the SFCL was performed. By applying the proposed correction method in the OCR, the protection coordination of OCRs for the application of SFCL in power distribution systemwithDGwas confirmed to be improved through the suppression of the malfunction of the OCR.
引用
收藏
页数:6
相关论文
共 50 条