Dominant frequency characteristics analysis of reclosing transient overvoltage in 10 kV cable-overhead hybrid line

被引:3
|
作者
Li, Jiaming [1 ]
Chen, Xi [1 ]
Xu, Long [1 ]
Zhao, Aixuan [1 ]
Deng, Junbo [1 ]
Zhang, Guanjun [1 ]
机构
[1] Xi An Jiao Tong Univ, State Key Lab Elect Insulat & Power Equipment, Xian 710049, Shaanxi, Peoples R China
基金
中国国家自然科学基金;
关键词
Cable-OHL hybrid line; Reclosing overvoltage; Dominant frequency; Modal theory; ATP-EMTP; WAVE-PROPAGATION;
D O I
10.1016/j.epsr.2019.106052
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Studying the characteristics of reclosing overvoltage is of great importance for risk assessment of reclosing in the cable-overhead hybrid networks because transient overvoltage (TOV) at different dominant frequency can have quite different negative effect to cable insulation. In a hybrid line, when a cable connects with an overhead line (OHL), the surge propagation can become very complex. To clarify the frequency characteristics of the reclosing transient overvoltage in a 10 kV hybrid line, in this paper, the simulations are carried out using ATP-EMTP (Alternative Transients Program, Electro-Magnetic Transients Program). The traditional approach to estimate the dominant frequency is suitable for pure cable-based or overhead line-based networks. However, for a hybrid line, due to the difference in line parameters between the cable and OHL, the characteristics of dominant frequency is investigated based on the distributed-parameter theory with new boundary conditions at the junction. According to the variation of dominant frequency considering the source impedance and the wave propagation in the modal domain, the non-monotonous variation of TOV with cable proportion is analyzed. The frequency calculation and the TOV analysis are verified by ATP-EMTP simulation.
引用
收藏
页数:10
相关论文
共 39 条
  • [21] Analysis of Transient Operating Characteristics of the 10 Kv Tri-Axial HTS Cable Under Fault Current
    Guan, Guangyu
    Feng, Bin
    Ding, Kaizhong
    Zhu, Jiahui
    Wei, Defu
    Cao, Jingying
    Liu, Jiaxin
    Chen, Jie
    Du, Shuangsong
    Du, Dingqing
    Dong, Yujun
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2021, 31 (08)
  • [22] Transient Stability Assessment of SMIB System with "Mixed" Overhead-Cable Line - Sensitivity Analysis
    Ippolito, Mariano G.
    Massaro, Fabio
    Morana, Giuseppe
    Musca, Rossano
    UPEC: 2009 44TH INTERNATIONAL UNIVERSITIES POWER ENGINEERING CONFERENCE, 2009, : 73 - 77
  • [23] Influence of frequency-dependent characteristics of grounding and line models on transient overvoltages in overhead lines
    Alipio, Rafael
    De Miranda, Audine
    PRZEGLAD ELEKTROTECHNICZNY, 2018, 94 (02): : 1 - 4
  • [24] Frequency-domain transient analysis in double-circuit mixed HV overhead line-cable connection including cross-bonding
    Wu, Lei
    Wouters, Peter A. A. F.
    Steennis, Fred E.
    INTERNATIONAL TRANSACTIONS ON ELECTRICAL ENERGY SYSTEMS, 2016, 26 (07): : 1408 - 1426
  • [25] Distribution Characteristics of Induced Overvoltage Along 10 kV Distribution Line Caused by Artificially Triggered Lightning at 40 m
    Cai, Li
    Xu, Changfeng
    Cao, Jinxin
    Chu, Wangxiang
    Wang, Jianguo
    Zhou, Mi
    Fan, Yadong
    IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2024, 66 (01) : 195 - 203
  • [26] Fault Location Identification of a Hybrid HVDC-VSC System Containing Cable and Overhead line Segments Using Transient Data
    Al Hassan, Hashim A.
    Grainger, Brandon M.
    McDermott, Thomas E.
    Reed, Gregory F.
    2016 IEEE/PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXPOSITION (T&D), 2016,
  • [27] Analysis of Transient Characteristics in the 110kV Cable Joint System during Switch Closing
    Wang, Huanan
    Wang, Xia
    Yu, Dong
    Shu, Zihang
    Wu, Kai
    2019 2ND INTERNATIONAL CONFERENCE ON ELECTRICAL MATERIALS AND POWER EQUIPMENT (ICEMPE 2019), 2019, : 395 - 399
  • [28] Waveform Analysis on Characteristics of Lightning Induced Overvoltages on 10kV Overhead Distribution Lines
    Yang Q.
    Zhang X.
    Sun J.
    Xu W.
    He W.
    Wang K.
    Qin Z.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2022, 42 (24): : 8900 - 8909
  • [29] Parameter Estimation for a 500 kV Overhead Transmission Line and Analysis of Dead Time Prior to Single-Phase Automatic Reclosing Based on Synchrophasor Measurements
    Ivanov, I.E.
    Umnov, Ya. A.
    Lachugin, V.F.
    Power Technology and Engineering, 2024, 58 (01) : 169 - 179
  • [30] Study on Propagation Characteristics of High Frequency Signal in 10 kV Single Core Crosslinking Polyethylene Power Cable
    Liang Jianfeng
    Li Binglin
    Duan Jiandong
    Xue Bing
    2017 IEEE CONFERENCE ON ENERGY INTERNET AND ENERGY SYSTEM INTEGRATION (EI2), 2017, : 556 - 561