Novel Method for Partial Discharge Detection in Gas Insulated Substation

被引:0
|
作者
Wang, Chuanning [1 ]
Liu, Baowen [2 ]
Xu, Honghua [1 ]
Jin, Jiping [3 ]
Ma, Hongzhong [2 ]
机构
[1] State Grid Jiangsu Nanjing Power Supply Co, Nanjing 210019, Jiangsu, Peoples R China
[2] Hohai Univ, Coll Energy & Elect Engn, Nanjing 211100, Jiangsu, Peoples R China
[3] Xian Boneng Power Technol Co Ltd, Xian 710065, Peoples R China
关键词
GIS; partial discharge; vibration; current pulse repetition; eddy current; circulating current; GIS;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
For the insulation diagnosis of electrical imaterials in power apparatus, partial discharge (PD) measurement has been recognized as an important tool. In this paper, electrical and mechanical methods were combined for the detection of the PD defect. To analyze the fundamental frequency vibration, the induced current including eddy current and circulating current in GIS was analyzed firstly. Then, PD pulses and vibrations on enclosure were measured on a 252kV GIS PD test system. PD faults included protrusion and insulator flashover. The phase of the pulse current of the two kinds of PD defects was analyzed. Meanwhile, the frequency spectrum of vibration on the GIS equipment was analyzed. In order to diagnose the partial discharge fault better, the relationship between the pulse current signals with the vibration signal was established. A more reliable PD detection method was proposed by combining with the electrical signal and the vibration signal.
引用
收藏
页数:4
相关论文
共 50 条
  • [31] Gas Insulated Substation GIS
    Bolin, Phil
    Koch, Hermann
    2006 POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1-9, 2006, : 1309 - 1311
  • [32] Gas insulated substation GIS
    Bolin, Phil
    Koch, Hermann
    2008 IEEE/PES TRANSMISSION & DISTRIBUTION CONFERENCE & EXPOSITION, VOLS 1-3, 2008, : 1058 - +
  • [33] Partial discharge and its application to gas insulated switchgear
    Yamagiwa, T
    Endo, F
    GASEOUS DIELECTRICS X, 2004, : 113 - 122
  • [34] A Coplanar Waveguide Based Antenna for Partial Discharge Detection in Gas-insulated Switchgear
    Darwish, Ahmad
    Refaat, Shady S.
    Abu-Rub, Haitham
    Coapes, Graeme
    3RD INTERNATIONAL CONFERENCE ON SMART GRID AND RENEWABLE ENERGY (SGRE), 2022,
  • [35] PARTIAL DISCHARGE DIAGNOSTICS FOR GAS-INSULATED SUBSTATIONS
    PEARSON, JS
    FARISH, O
    HAMPTON, BF
    JUDD, MD
    TEMPLETON, D
    PRYOR, BM
    WELCH, IM
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1995, 2 (05) : 893 - 905
  • [36] Study of Polarization Sensitivity of UHF Sensor for Partial Discharge Detection in Gas Insulated Switchgear
    Yadam, Yugandhara Rao
    Ramanujam, Sarathi
    Arunachalam, Kavitha
    IEEE SENSORS JOURNAL, 2023, 23 (02) : 1214 - 1223
  • [37] A Flexible Planarized Biconical Antenna for Partial Discharge Detection in Gas-Insulated Switchgear
    Zhang, Guozhi
    Tian, Jinwen
    Zhang, Xiaoxing
    Liu, Jianben
    Lu, Changyue
    IEEE ANTENNAS AND WIRELESS PROPAGATION LETTERS, 2022, 21 (12): : 2432 - 2436
  • [38] Two Planar Antennas for Detection of Partial Discharge in Gas-Insulated Switchgear (GIS)
    Lozano-Claros, Diego
    Custovic, Eddie
    Elton, Darrell
    2015 IEEE INTERNATIONAL CONFERENCE ON COMMUNICATION, NETWORKS AND SATELLITE (COMNESTAT), 2015, : 8 - 15
  • [39] Radiometer Monitoring System for Partial Discharge Detection in Substation
    Zhang, Y.
    Neto, J. M.
    Upton, D.
    Jaber, A.
    Khan, U.
    Saeed, B.
    Ahmed, H.
    Mather, P.
    Atkinson, R.
    Neto, J. S.
    Vieira, M. F. Q.
    Lazaridis, P.
    Glover, I. A.
    2015 1st URSI Atlantic Radio Science Conference (URSI AT-RASC), 2015,
  • [40] PD test in Gas Insulated Substation using UHF method
    Prabakaran, T.
    Powl, John S.
    Uppili, B.
    2015 International Conference on Condition Assessment Techniques in Electrical Systems (CATCON), 2015, : 57 - 60