Field study of cooling performance of two ground-source heat pumps in Canadian single-family houses

被引:9
作者
Abdel-Salam, Mohamed R. H. [1 ]
Zaidi, Aqeel [1 ]
机构
[1] Enbridge Gas Inc, Technol & Dev, 500 Consumers Rd, Toronto, ON M2J 1P8, Canada
关键词
Ground-source heat pump; Coefficient of performance (COP); Energy efficiency; Air-conditioning; Residential buildings; SYSTEM; EXPERIENCE; ENERGY; WATER;
D O I
10.1016/j.applthermaleng.2020.116294
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper is the first part of a two-part study of the performance of ground-source heat pumps (GSHPs) in single-family detached houses in Canada. In this paper, the cooling performance of two 4-ton (14 kW) vertical closed-loop water-to-air GSHP systems installed in two single-family detached houses in Innisfil (80 km north of Toronto, Canada) is monitored, analyzed and evaluated over one cooling season. Results show that the seasonal coefficient of performance of heat pump (COPhp) and GSHP system (COPsys) are 12.9 and 11.0, respectively. Unlike conventional air-conditioners, the outdoor air temperature had a small influence on the COP of the tested GSHPs. The average temperature of water leaving the ground loop was 12 degrees C and the leaving water temperature varied by up to 3.7 degrees C throughout the cooling season. The total power consumption and operating cost of the tested GSHPs are less than conventional air-conditioners by up to 66%.
引用
收藏
页数:15
相关论文
共 18 条
  • [1] Abdel-Salam M.R.H.., 2020, ENERGY BUILDIN UNPUB
  • [2] Exergy analysis of a two-stage ground source heat pump with a vertical bore for residential space conditioning under simulated occupancy
    Ally, Moonis R.
    Munk, Jeffrey D.
    Baxter, Van D.
    Gehl, Anthony C.
    [J]. APPLIED ENERGY, 2015, 155 : 502 - 514
  • [3] Ashrae, 2013, STANDARD 55 THERMAL
  • [4] Air-conditioning of a typical house in moderate climates with Ground Source Heat Pumps and cost comparison with Air Source Heat Pumps
    Christodoulides, Paul
    Aresti, Lazaros
    Florides, Georgios
    [J]. APPLIED THERMAL ENGINEERING, 2019, 158
  • [5] Cooling performance of a vertical ground-coupled heat pump system installed in a school building
    Hwang, Yujin
    Lee, Jae-Keun
    Jeong, Young-Man
    Koo, Kyung-Min
    Lee, Dong-Hyuk
    Kim, In-Kyu
    Jin, Sim-Won
    Kim, Soo H.
    [J]. RENEWABLE ENERGY, 2009, 34 (03) : 578 - 582
  • [6] Experimental investigation of the cooling performance of a ground source heat pump system in Denizli, Turkey
    Karabacak, Rasim
    Acar, Sengul Guven
    Kumsar, Halil
    Gokgoz, Ali
    Kaya, Mustafa
    Tulek, Yahya
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2011, 34 (02): : 454 - 465
  • [7] Potential of ground source heat pump systems in cooling-dominated environments: Residential buildings
    Kharseh, Mohamad
    Al-Khawaja, Mohammed
    Suleiman, Muhannad T.
    [J]. GEOTHERMICS, 2015, 57 : 104 - 110
  • [8] Heating and cooling performance analysis of a ground source heat pump system in Southern Germany
    Luo, Jin
    Rohn, Joachim
    Bayer, Manfred
    Priess, Anna
    Wilkmann, Lucas
    Xiang, Wei
    [J]. GEOTHERMICS, 2015, 53 : 57 - 66
  • [9] Operation characteristics and experience of a ground source heat pump system with a vertical ground heat exchanger
    Michopoulos, A.
    Zachariadis, T.
    Kyriakis, N.
    [J]. ENERGY, 2013, 51 : 349 - 357
  • [10] Experimental and modeling analysis of a ground source heat pump system
    Montagud, Carla
    Miguel Corberan, Jose
    Ruiz-Calvo, Felix
    [J]. APPLIED ENERGY, 2013, 109 : 328 - 336