Thermal Performance and Energy Saving Analysis of Indoor Air-Water Heat Exchanger Based on Micro Heat Pipe Array for Data Center

被引:10
作者
Jing, Heran [1 ]
Quan, Zhenhua [1 ]
Zhao, Yaohua [1 ]
Wang, Lincheng [1 ]
Ren, Ruyang [1 ]
Liu, Zichu [1 ]
机构
[1] Beijing Univ Technol, Beijing Key Lab Green Built Environm & Energy Eff, Beijing 100124, Peoples R China
基金
中国国家自然科学基金;
关键词
data center; natural cold energy; micro-heat pipe array; heat transfer performance; energy efficiency; COOLING SYSTEMS; WASTE HEAT; SIMULATION; OPTIMIZATION; MODULE; FLOW;
D O I
10.3390/en13020393
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
According to the temperature regulations and high energy consumption of air conditioning (AC) system in data centers (DCs), natural cold energy becomes the focus of energy saving in data center in winter and transition season. A new type of air-water heat exchanger (AWHE) for the indoor side of DCs was designed to use natural cold energy in order to reduce the power consumption of AC. The AWHE applied micro-heat pipe arrays (MHPAs) with serrated fins on its surface to enhance heat transfer. The performance of MHPA-AWHE for different inlet water temperatures, water and air flow rates was investigated, respectively. The results showed that the maximum efficiency of the heat exchanger was 81.4% by using the effectiveness number of transfer units (epsilon-NTU) method. When the max air flow rate was 3000 m(3)/h and the water inlet temperature was 5 degrees C, the maximum heat transfer rate was 9.29 kW. The maximum pressure drop of the air side and water side were 339.8 Pa and 8.86 kPa, respectively. The comprehensive evaluation index j/f(1/2) of the MHPA-AWHE increased by 10.8% compared to the plate-fin heat exchanger with louvered fins. The energy saving characteristics of an example DCs in Beijing was analyzed, and when the air flow rate was 2500 m(3)/h and the number of MHPA-AWHE modules was five, the minimum payback period of the MHPA-AWHE system was 2.3 years, which was the shortest and the most economical recorded. The maximum comprehensive energy efficiency ratio (EER) of the system after the transformation was 21.8, the electric power reduced by 28.3% compared to the system before the transformation, and the control strategy was carried out. The comprehensive performance provides a reference for MHPA-AWHE application in data centers.
引用
收藏
页数:24
相关论文
共 37 条
[1]   Reducing Data Center Energy Consumption Through Peak Shaving and Locked-In Energy Avoidance [J].
Alanazi, Sultan ;
Dabbagh, Mehiar ;
Hamdaoui, Bechir ;
Guizani, Mohsen ;
Zorba, Nizar .
IEEE TRANSACTIONS ON GREEN COMMUNICATIONS AND NETWORKING, 2017, 1 (04) :551-562
[2]   Heat transfer characteristics of a natural circulation separate heat pipe under various operating conditions [J].
Bai, Ye ;
Wang, Liang ;
Zhang, Shuang ;
Xie, Ningning ;
Chen, Haisheng .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2018, 126 :191-200
[3]   A steady-state model for the design and optimization of a centralized cooling system [J].
Beitelmal, Abdlmonem H. ;
Patel, Chandrakant D. .
INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2010, 34 (14) :1239-1248
[4]   Viability of datacenter cooling systems for energy efficiency in temperate or subtropical regions: Case study [J].
Cho, Jinkyun ;
Lim, Taesub ;
Kim, Byungseon Sean .
ENERGY AND BUILDINGS, 2012, 55 :189-197
[5]  
Da Y, 2004, HV&AC, V34, P48
[6]   Simultaneous use of air-side and water-side economizers with the air source heat pump in a data center for cooling and heating production [J].
Deymi-Dashtebayaz, Mandi ;
Namanlo, Sajjad Valipour ;
Arabkoohsar, Ahmad .
APPLIED THERMAL ENGINEERING, 2019, 161
[7]   Experimental study on the heat recovery characteristic of a heat exchanger based on a flat micro-heat pipe array for the ventilation of residential buildings [J].
Diao, Y. H. ;
Liang, L. ;
Kang, Y. M. ;
Zhao, Y. H. ;
Wang, Z. Y. ;
Zhu, T. T. .
ENERGY AND BUILDINGS, 2017, 152 :448-457
[8]   An Experimental Investigation on Heat Transfer Characteristics for Micro-Capillary Evaporator [J].
Diao, Y. H. ;
Liu, J. R. ;
Wang, Y. ;
Zhao, Y. H. .
EXPERIMENTAL HEAT TRANSFER, 2009, 22 (02) :87-98
[9]   Simulation of a temperature adaptive control strategy for an IWSE economizer in a data center [J].
Durand-Estebe, Baptiste ;
Le Bot, Cedric ;
Mancos, Jean Nicolas ;
Arquis, Eric .
APPLIED ENERGY, 2014, 134 :45-56
[10]   Integrative modelling and optimisation of a desiccant cooling system coupled with a photovoltaic thermal-solar air heater [J].
Fan, Wenke ;
Kokogiannakis, Georgios ;
Ma, Zhenjun .
SOLAR ENERGY, 2019, 193 :929-947