S-Transform Based Pilot Protection Method for HVDC Transmission Lines

被引:0
|
作者
Li, Zhao [1 ]
Zou, Guibin [1 ]
Du, Tao [1 ]
Yang, Wenjia [2 ]
机构
[1] Shandong Univ, Sch Elect Engn, Jinan, Peoples R China
[2] State Grid Shandong Power Supply Co, Weifang Power Supply Co, Weifang, Peoples R China
关键词
high voltage direct current(HVDC) transmission line; fault components of voltage and current; S transform; faulted line; pilot protection;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Traditional traveling wave protection of HVDC line is easily influenced by fault resistance, and the current differential protection as backup protection has disadvantages of slow operation speed and data synchronization, so this paper proposes a pilot protection method for HVDC line based on S transform. Theoretical analysis shows, for a fault occurring on the forward direction of the protection, the polarities of the fault components of voltage and current detected by protection are opposite, but for a backward direction fault, they are the same. According to these characteristics, a new method based on S transform angle differences to identify the fault direction is presented. In addition, for a pole-earth fault in bipolar HVDC systems, the faulted line can be distinguished from the healthy line in terms of ratio differences of S transform transient voltage energies. Simulation results show that the proposed method can effectively identify internal and external faults, the faulted line and lightning disturbance in different fault conditions.
引用
收藏
页码:1667 / 1672
页数:6
相关论文
共 50 条
  • [1] Boundary Protection of HVDC Transmission Lines Based on Generalized S-transform
    Zhang Y.
    Li D.
    Zhang S.
    Li J.
    Yin J.
    Gaodianya Jishu/High Voltage Engineering, 2018, 44 (10): : 3197 - 3206
  • [2] A novel directional pilot protection method for EHV transmission lines based on S-transform and SVM
    Zhenwei Guo
    Yingcai Deng
    Tong Zhang
    Zebo Huang
    Discover Applied Sciences, 7 (4)
  • [3] S-Transform Based Traveling Wave Directional Pilot Protection for Hybrid LCC-MMC-HVDC Transmission Line
    Zhang, Wei
    Wang, Dong
    ENERGIES, 2022, 15 (13)
  • [4] Polarity comparison pilot protection based on S-transform energy relative entropy for high voltage transmission lines
    Li, Xiaopeng
    He, Zhengyou
    Wu, Xiao
    Dianwang Jishu/Power System Technology, 2014, 38 (08): : 2250 - 2256
  • [5] A Fast Non-Unit Protection Method Based on S-Transform for HVDC Line
    Zou, Guibin
    Li, Zhao
    Sun, Chenjun
    Gao, Houlei
    ELECTRIC POWER COMPONENTS AND SYSTEMS, 2018, 46 (04) : 472 - 482
  • [6] Single Ring Theorem Based Pilot Protection Method for HVDC Transmission Lines
    Liu X.
    Yue S.
    Yang D.
    Wang W.
    Dianwang Jishu/Power System Technology, 2021, 45 (01): : 162 - 169
  • [7] S-Transform Assisted CUSUM Based Protection Strategy for Transmission Lines Possessing UPFC
    Biswas, Sauvik
    Parhi, Vishal
    Anudeep, Bhatraj
    Nayak, Paresh Kumar
    2020 INTERNATIONAL CONFERENCE ON EMERGING FRONTIERS IN ELECTRICAL AND ELECTRONIC TECHNOLOGIES (ICEFEET 2020), 2020,
  • [8] A Single-Terminal Traveling Wave Fault Location Method for VSC-HVDC Transmission Lines Based on S-transform
    Xi, Chuanxin
    Chen, Qing
    Wang, Lei
    2016 IEEE PES ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2016, : 1008 - 1012
  • [9] A novel S-Transform-based pilot protection algorithm for transmission lines
    Guo, Zhenwei
    Deng, Yingcai
    Huang, Jiemei
    Zhang, Tong
    Huang, Zebo
    ELECTRIC POWER SYSTEMS RESEARCH, 2025, 241
  • [10] A pilot protection scheme for HVDC transmission lines based on boundary energy
    Yang, Yayu
    Tai, Nengling
    Liu, Jian
    Zheng, Xiaodong
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2015, 35 (22): : 5757 - 5767