Model Predictive Control of a Voltage-Source Inverter With Seamless Transition Between Islanded and Grid-Connected Operations

被引:168
作者
Li, Xiao [1 ]
Zhang, Haiyu [1 ]
Shadmand, Mohammad B. [1 ]
Balog, Robert S. [1 ]
机构
[1] Texas A&M Univ, Dept Elect & Comp Engn, College Stn, TX 77840 USA
关键词
Grid-connected mode; islanded mode; model predictive control (MPC); seamless transfer; stability; synchronization algorithm; weight factor tuning; CONTROL STRATEGY; STAND-ALONE; POWER CONVERTERS; PLL;
D O I
10.1109/TIE.2017.2696459
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
Inverter-based distributed generation (DG) system is becoming an attractive solution for high penetration of renewable energy sources to the main grid. DG system should be able to supply power to the local loads whenever necessary even in case of utility power outage. Thus, the inverters in DG systems are expected to operate in both grid-connected and islanded mode, where they are acting as a current source for the ac grid and a voltagesource for the load, respectively. Transition between modes of operation is nontrivial and can cause deviations in voltage and current, because of mismatch in frequency, phase, and amplitude between the inverter output voltage and the grid voltage. Thus, it is necessary to have seamless transition between grid-connected and islanded mode. This paper presents a new control strategy with seamless transfer characteristics for a grid-connected voltage-source inverter using model predictive control (MPC) framework. The main objectives of the proposed predictive controller are: 1) decoupled power control in grid-connected mode, which enables the proposed power electronics interface to provide ancillary services such as reactive power compensation; 2) load voltage control in islanded mode; and 3) seamless transition between modes of operation through proposed synchronization and phase adjustment algorithm. The proposed controller features simplicity to implement since only one cost function should be minimized for all modes of operation, and hence no ambiguity in the control algorithm that could cause mode transition problems. An autotuning strategy for weight factors inMPC cost function is proposed to simplify the weight factor tuning strategy. The stability analysis of the proposed controller is provided. Simulation and experimental results validate the expected performance and effectiveness of the proposed control strategy.
引用
收藏
页码:7906 / 7918
页数:13
相关论文
共 38 条
[1]   Transition Control Strategy Between Standalone and Grid-Connected Operations of Voltage-Source Inverters [J].
Arafat, Md. Nayeem ;
Palle, Sreeshailam ;
Sozer, Yilmaz ;
Husain, Iqbal .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2012, 48 (05) :1516-1525
[2]   Vector Control of Single-Phase Voltage-Source Converters Based on Fictive-Axis Emulation [J].
Bahrani, Behrooz ;
Rufer, Alfred ;
Kenzelmann, Stephan ;
Lopes, Luiz A. C. .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2011, 47 (02) :831-840
[3]   Basic Principles of MPC for Power Converters [J].
Bordons, Carlos ;
Montero, Carlos .
IEEE INDUSTRIAL ELECTRONICS MAGAZINE, 2015, 9 (03) :31-43
[4]  
Camm E. H., 2009, 2009 IEEE POW EN SOC, P1, DOI [10.1109/pes.2009.5275322, 10.1109/PES.2009.5275322, DOI 10.1109/PES.2009.5275322]
[5]   An Islanding Detection Algorithm for Inverter-Based Distributed Generation Based on Reactive Power Control [J].
Chen, Xiaolong ;
Li, Yongli .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2014, 29 (09) :4672-4683
[6]   Guidelines for Weighting Factors Design in Model Predictive Control of Power Converters and Drives [J].
Cortes, Patricio ;
Kouro, Samir ;
La Rocca, Bruno ;
Vargas, Rene ;
Rodriguez, Jose ;
Leon, Jose I. ;
Vazquez, Sergio ;
Franquelo, Leopoldo G. .
2009 IEEE INTERNATIONAL CONFERENCE ON INDUSTRIAL TECHNOLOGY, VOLS 1-3, 2009, :1477-1483
[7]   Modes of Operation and System-Level Control of Single-Phase Bidirectional PWM Converter for Microgrid Systems [J].
Dong, Dong ;
Thacker, Timothy ;
Cvetkovic, Igor ;
Burgos, Rolando ;
Boroyevich, Dushan ;
Wang, Fred ;
Skutt, Glenn .
IEEE TRANSACTIONS ON SMART GRID, 2012, 3 (01) :93-104
[8]   Grid to Standalone Transition Motion-Sensorless Dual-Inverter Control of PMSG With Asymmetrical Grid Voltage Sags and Harmonics Filtering [J].
Fatu, Marius ;
Blaabjerg, Frede ;
Boldea, Ion .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2014, 29 (07) :3463-3472
[9]   Predictive Current Control With Instantaneous Reactive Power Minimization for a Four-Leg Indirect Matrix Converter [J].
Garcia, Cristian F. ;
Rivera, Marco E. ;
Rodriguez, Jose R. ;
Wheeler, Pat W. ;
Pena, Ruben S. .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2017, 64 (02) :922-929
[10]  
Gu B, 2014, APPL POWER ELECT CO, P1788, DOI 10.1109/APEC.2014.6803548