A MHO distance relay device in EMTPWorks

被引:7
作者
Gerin-Lajoie, Luc [1 ]
机构
[1] Hydro Quebec TransEnergie, Planificat Actifs, Etud Reseaux, Montreal, PQ H5B 1H7, Canada
关键词
MHO distance relay; EMTP-RV; Protection;
D O I
10.1016/j.epsr.2008.09.010
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Distance relays are widely used for protection of transmission lines. Usually, the nonlinear nature of an arcing fault requires that a time model be implemented to determine if the relay detects or not this fault condition. Moreover, the mutual effect of line conductors for single or multiphase faults requires that all three phases of the relay be modelized. This paper describes in detail a first generic MHO distance relay in EMTPWorks based on three separate single-phase impedance vectors. Cosine-sine filters are used to perform the phasor representation of the fundamental current and voltage computed over a 50/60 Hz sliding time window, Validation of the measured impedance function of the model is compared with the real apparent impedance of the network. This paper also discusses logical operations to initiate the opening of line breakers. Crown Copyright (C) 2008 Published by Elsevier B.V. All rights reserved.
引用
收藏
页码:484 / 491
页数:8