Dynamic arc modeling based on computation of couple electric field and flow field for high voltage SF6 interrupter

被引:13
作者
Liu, XM [1 ]
Wang, EZ [1 ]
Cao, YD [1 ]
机构
[1] Shenyang Univ Technol, Sch Elect Engn, Shenyang, Peoples R China
关键词
electric field; flow field; interrupter; SF6;
D O I
10.1109/TMAG.2004.825462
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this paper, a dynamic arc model based on computation of coupled electric field and flow field for a high voltage (HV) SF6 interrupter has been investigated and analyzed. Moreover, for simulating the insulating performance and interrupting characteristics of the SF6 interrupter, dynamic variation of the arc in different interrupting cases, such as before current zero, approaching zero and after current zero have been established, and the compressibility and viscosity of SF6 gas in the whole interrupting course has been taken into consideration. Interrupting performance and dielectric recovery characteristic of the HV SF6 interrupter have been obtained and discussed. Fairly good representations of interrupting evolutionary processes within the are-quenching chamber and arc dynamic characteristics have been achieved using the proposed model. And interrupting performance with higher precision has been obtained.
引用
收藏
页码:601 / 604
页数:4
相关论文
共 4 条
[1]   COMPOSITION AND TRANSPORT PROPERTIES OF SE6 AND THEIR USE IN A SIMPLIFIED ENTHALPY FLOW ARC MODEL [J].
FROST, LS ;
LIEBERMA.RW .
PROCEEDINGS OF THE INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS, 1971, 59 (04) :474-&
[2]   RADIATION EMISSION COEFFICIENTS FOR SULFUR HEXAFLUORIDE ARC PLASMAS [J].
LIEBERMANN, RW ;
LOWKE, JJ .
JOURNAL OF QUANTITATIVE SPECTROSCOPY & RADIATIVE TRANSFER, 1976, 16 (03) :253-264
[3]  
YUNDONG C, 2001, IEEE T MAGN, V37, P3178
[4]  
YUNDONG C, 2001, THESIS SHENYANG U TE