New high-voltage directional and phase selection protection technique based on real power system data

被引:17
作者
Eissa, M. M. [1 ]
Mahfouz, M. M. A. [1 ]
机构
[1] Helwan Univ, Fac Engn, Dept Elect Engn, Cairo, Egypt
关键词
Electric power system protection;
D O I
10.1049/iet-gtd.2012.0319
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Traditional directional power and current protection requires the current and the voitage to be measured. The directional current protection equipment is only capable for tripping the faulty incomer. While the direction in which the fault occurs is detected by measuring the direction of current flow, or in other words the phase displacement between the current and voltage. This study introduces a directional protection technique with phase selection based on measuring the current only. The correlogram function principle is applied on two successive current cycles. The two cycles are based on the pre- and post-fault current signals. The ability to differentiate between a fault in one direction and others is obtained using the sign of correlogram coefficients while its magnitude is used to identify the faulted phase. A proposed directional relay characteristic with correlogram coefficients calculated pre- and during the fault are also introduced. Different cases of non-symmetrical faults have been studied on a real recorded fault data for 240-kV transmission system at the province of Alberta-Canada. The results showed that the proposed technique is simple and reliable not only to identify the fault direction but also to select the faulted phases.
引用
收藏
页码:1075 / 1085
页数:11
相关论文
共 18 条
[1]   An accurate fault classification technique for power system monitoring devices [J].
Adu, T .
IEEE TRANSACTIONS ON POWER DELIVERY, 2002, 17 (03) :684-690
[2]   A combined directional and faulted phase selector element based on incremental quantities [J].
Benmouyal, G ;
Mahseredjian, J .
IEEE TRANSACTIONS ON POWER DELIVERY, 2001, 16 (04) :478-484
[3]   An integrated protection scheme based on a distance approach [J].
Bo, Z. Q. ;
He, J. H. ;
Dong, X. Z. ;
Caunce, B. R. J. ;
Klimek, A. .
PROCEEDINGS OF THE 41ST INTERNATIONAL UNIVERSITIES POWER ENGINEERING CONFERENCE, VOLS 1 AND 2, 2006, :800-+
[4]  
Chatfield C., 2004, The analysis of time series: An introduction
[5]   Preface [J].
Chen, Jing ;
Lemyre, Louise ;
Wilkins, Ruth ;
Wilkinson, Diana .
RADIATION PROTECTION DOSIMETRY, 2010, 142 (01) :1-1
[6]   Study of wavelet-based ultra high speed directional transmission line protection [J].
Chen, W ;
Malik, OP ;
Yin, XG ;
Chen, DS ;
Zhang, Z .
IEEE TRANSACTIONS ON POWER DELIVERY, 2003, 18 (04) :1134-1139
[7]   Development and investigation of a new high-speed directional relay using field data [J].
Eissa, M. M. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (03) :1302-1309
[8]   A New Digital Feed Circuit Protection Using Directional Element [J].
Eissa, M. M. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (02) :531-537
[9]  
Jena P., 2009, 2009 INT C POW SYST, P1
[10]   Protection scheme for transmission lines based on alienation coefficients for current signals [J].
Masoud, M. E. ;
Mahfouz, M. M. A. .