Industrial batteries in the electric power system of 'Electricite de France'

被引:0
作者
Gagnol, P
机构
[1] Electricité de France, Direction des Etudes et Recherches, Les Renardières, 77250 Moret-sur-Loing
关键词
power systems; lead/acid batteries; hydrogen evolution; sizing; industrial batteries;
D O I
10.1016/S0378-7753(96)02523-2
中图分类号
O64 [物理化学(理论化学)、化学物理学];
学科分类号
070304 ; 081704 ;
摘要
More than 5000 industrial batteries are operating in the different power plants, substations and distribution centres of 'Electricite de France' (EDF). 2 V lead/acid and 1.2 V alkaline systems are used for different stationary stand-by applications: power station control, communication, etc. In nuclear plants, these batteries are part of the ultimate safety system ensuring the safe control of the reactor. The operating conditions of the industrial batteries at EDF, the different related battery technologies and the testing methods used to assess their operating ability are described. For selection, batteries undergo electric, seismic and ageing tests. Ageing sequences involve successive floating phases at a high temperature. Results on absorptive glass mat valve-regulated lead/acid battery testing are given. On-line monitoring methods are studied in order to evaluate the remaining available autonomy of the battery according to its state of ageing. In addition to these stand-by applications, EDF is also investigating the potential of future energy and quality applications of stationary batteries such as load levelling or storage of energy produced from renewable sources.
引用
收藏
页码:203 / 208
页数:6
相关论文
共 7 条
  • [1] ALZIEU J, 1989, P SEE C ACC EL JOURN, P213
  • [2] DEFLANDRE T, 1994, HM229441A
  • [3] GAGNOL P, 1995, P 1 EUREL C EL STOR, P71
  • [4] LEROY J, 1994, LABECHO, V1, P2
  • [5] LEROY J, 1992, HM172334
  • [6] MARQUET A, 1994, P EL ENG EN MAY 1994
  • [7] MORANGE M, 1989, P SEE C ACC EL JOURN, P229