Interval valued data driven approach for sensor fault detection of nonlinear uncertain process

被引:24
作者
Lahdhiri, Hajer [1 ]
Taouali, Okba [1 ,2 ]
机构
[1] Univ Monastir, Natl Engn Sch Monastir, Monastir, Tunisia
[2] Univ Tabuk, Fac Comp & Informat Technol, Dept Comp Engn, Tabuk, Saudi Arabia
关键词
Reduced Rank KPCA; Nonlinear process monitoring; Fault detection; Fault isolation; Tennessee Eastman Process (TEP); PRINCIPAL COMPONENT ANALYSIS; DIAGNOSIS; GLRT; PCA; STRATEGY; KPCA;
D O I
10.1016/j.measurement.2020.108776
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
In advanced industrial fields such as chemical processes, faults must absolutely be detected; we cannot afford to operate with failing operative parts. It is therefore, necessary to take into consideration the uncertainties in order to establish a guaranteed failure detection. For this propose, several approaches have been introduced in the literature based on the Principal Components Analysis (PCA) approach for interval-valued data. However, these developed approaches treated only the linear process models. To overcome this drawback, recently, the researchers proposed to extend monitoring process based on Kernel Principal Components Analysis (KPCA) approach to the nonlinear uncertain case, in which two models are developed: model based on the lower bound (LB) and upper bound (UB) and model based on midpoints and radii. Nevertheless, the number of variables that adequately represent the normal operating condition of system can be very large. To deal with both high calculation costs and the memory storage, in this paper, we suggest an improved kernel method, in order to ameliorate failure detection process for nonlinear uncertain system. The suggested method, fuse the benefit of Interval Kernel Generalized Likelihood Ratio Test (IKGLRT) index with the Exponentially Weighted Moving Average (EWMA) filter and the Interval Reduced Kernel Principal Component (IRR-KPCA). The failure detection performance of the suggested method is valued using a Tennessee Eastman Process (TEP).
引用
收藏
页数:9
相关论文
共 52 条
[1]   Sensor fault detection based on principal component analysis for interval-valued data [J].
Ait-Izem, Tarek ;
Harkat, M. -Faouzi ;
Djeghaba, Messaoud ;
Kratz, Frederic .
QUALITY ENGINEERING, 2018, 30 (04) :635-647
[2]   On the application of interval PCA to process monitoring: A robust strategy for sensor FDI with new efficient control statistics [J].
Ait-Izem, Tarek ;
Harkat, M-Faouzi ;
Djeghaba, Messaoud ;
Kratz, Frederic .
JOURNAL OF PROCESS CONTROL, 2018, 63 :29-46
[3]  
Alcala C. F., 2011, THESIS ECOLE USC U
[4]  
[Anonymous], 1997, Revue de Statistique Appliquee
[5]   Kernel PLS-based GLRT method for fault detection of chemical processes [J].
Botre, Chiranjivi ;
Mansouri, Majdi ;
Nounou, Mohamed ;
Nounou, Hazem ;
Karim, M. Nazmul .
JOURNAL OF LOSS PREVENTION IN THE PROCESS INDUSTRIES, 2016, 43 :212-224
[6]   Diagnosis of uncertain nonlinear systems using interval kernel principal components analysis: Application to a weather station [J].
Chakour, Chouaib ;
Benyounes, Abdelhafid ;
Boudiaf, Mahmoud .
ISA TRANSACTIONS, 2018, 83 :126-141
[7]  
Chouakria A., 1998, Extension Des Methodes D'Analyse Factorielle a Des Donnees de Type Intervalle
[8]   A PLANT-WIDE INDUSTRIAL-PROCESS CONTROL PROBLEM [J].
DOWNS, JJ ;
VOGEL, EF .
COMPUTERS & CHEMICAL ENGINEERING, 1993, 17 (03) :245-255
[9]   A new fault detection method for nonlinear process monitoring [J].
Fazai, Radhia ;
Taouali, Okba ;
Harkat, Mohamed Faouzi ;
Bouguila, Nasereddine .
INTERNATIONAL JOURNAL OF ADVANCED MANUFACTURING TECHNOLOGY, 2016, 87 (9-12) :3425-3436
[10]   Online reduced kernel GLRT technique for improved fault detection in photovoltaic systems [J].
Fezai, R. ;
Mansouri, M. ;
Trabelsi, M. ;
Hajji, M. ;
Nounou, H. ;
Nounou, M. .
ENERGY, 2019, 179 :1133-1154