Seasonal variation of air quality in hospitals with indoor-outdoor correlations

被引:52
作者
Chamseddine, A. [1 ]
Alameddine, I [1 ]
Hatzopoulou, M. [2 ]
El-Fadel, M. [1 ]
机构
[1] Amer Univ Beirut, Dept Civil & Environm Engn, Beirut, Lebanon
[2] Univ Toronto, Dept Civil & Environm Engn, Toronto, ON, Canada
关键词
Hospital environment; Indoor air quality; Seasonal trends; Indoor and outdoor correlation; PARTICULATE MATTER CONCENTRATIONS; SICK BUILDING SYNDROME; PM2.5; CONCENTRATION; CARBON-MONOXIDE; MINERAL DUST; HEALTH; PARTICLES; POLLUTION; PM10; SYMPTOMS;
D O I
10.1016/j.buildenv.2018.11.034
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This study involved a seasonal exposure assessment in a hospital environment using several air quality indicators including carbon monoxide (CO), carbon dioxide (CO2), particulate matter (PM10, and PM2.5), and total volatile organic compounds (TVOCs). We examined the distribution of and variation in the indoor and outdoor pollutant concentrations in 12 working areas across three hospitals, with an emphasis on capturing seasonal variations. We assessed correlations between measured indoor and outdoor levels to quantify the importance of indoor sources on air quality relative to outdoor sources. Our results indicated that while indoor and outdoor CO levels were below air quality standards/guidelines, measured PM2.5 and PM10, concentrations at several locations exceeded the standards 2- to 3.5-fold. We generally recorded higher indoor PM levels during the warm season, particularly during regional desert storm events. The ingress of particles from the outdoor to indoor environment was evident with high correlations between indoor and outdoor PM2.5 (r between 0.83 and 0.92) and PM10, (r between 0.74 and 0.86) levels, particularly during the warm season. Indoor to outdoor (I/O) ratios of PM2.5 and PM10, were mostly < 1. In contrast, indoor levels of CO2 and TVOCs exceeded outdoor concentrations during both the warm and cold seasons with I/O ratios > 1 across all sampling locations. Our paper concludes with implications of high PM exposure and a suggested management framework for limiting such exposure in hospitals.
引用
收藏
页码:689 / 700
页数:12
相关论文
共 95 条
[1]   A review of standards and guidelines set by international bodies for the parameters of indoor air quality [J].
Abdul-Wahab, Sabah Ahmed ;
En, Stephen Chin Fah ;
Elkamel, Ali ;
Ahmadi, Lena ;
Yetilmezsoy, Kaan .
ATMOSPHERIC POLLUTION RESEARCH, 2015, 6 (05) :751-767
[2]   Effect of an Air Cleaner with Electrostatic Filter on the Removal of Airborne House Dust Mite Allergens [J].
Agrawal, Santosh Rani ;
Kim, Hak-Joon ;
Lee, Yong Won ;
Sohn, Jung-Ho ;
Lee, Jae Hyun ;
Kim, Yong-Jin ;
Lee, Sung-Hwa ;
Hong, Chein-Soo ;
Park, Jung-Won .
YONSEI MEDICAL JOURNAL, 2010, 51 (06) :918-923
[3]  
[Anonymous], 2002, EH40 2005 WORKPL EXP
[4]  
[Anonymous], 2004, VENT ACC IND AIR QUA
[5]  
[Anonymous], REGULATIONS RECOMMEN
[6]  
[Anonymous], CARD DIS AIR POLL
[7]  
[Anonymous], 2009, TURKEY NOBEL MEDICUS
[8]  
[Anonymous], 2010, 621 ASHRAE
[9]  
[Anonymous], INFECT ECOL EPIDEMIO
[10]  
[Anonymous], 2003, REV AN TIM SER STUD