A heuristic procedure for the automatic creation of district metered areas in water distribution systems

被引:81
作者
Alvisi, S. [1 ]
Franchini, M. [1 ]
机构
[1] Univ Ferrara, Dept Engn, I-44100 Ferrara, Italy
关键词
district metered area; water distribution system; graph theory; breadth first search; SCHEME;
D O I
10.1080/1573062X.2013.768681
中图分类号
TV21 [水资源调查与水利规划];
学科分类号
081501 ;
摘要
This paper presents a procedure for the automatic creation of district metered areas (DMAs) in a water distribution system. The procedure uses techniques derived from graph theory (Breadth First Search and algorithm for finding the shortest paths in a graph) and demand-driven hydraulic simulations of the network in order to (a) divide the nodes among an assigned number of DMAs, (b) identify the open' links between districts where flow meters will be placed and (c) identify the closed' links between districts where isolation valves will be placed. The application of the proposed procedure to the case of a real water distribution system revealed it to be robust and effective. In particular, the results obtained show that the procedure makes it possible to identify very good solutions in terms of resilience and minimum pressures when reference to the peak demand and fire-flow conditions is made. The resulting performance indicators were better than those obtainable by applying a similar procedure previously proposed in the scientific literature.
引用
收藏
页码:137 / 159
页数:23
相关论文
共 31 条
[1]   Segment identification in water distribution systems [J].
Alvisi, S. ;
Creaco, E. ;
Franchini, M. .
URBAN WATER JOURNAL, 2011, 8 (04) :203-217
[2]   A short-term, pattern-based model for water-demand forecasting [J].
Alvisi, Stefano ;
Franchini, Marco ;
Marinelli, Alberto .
JOURNAL OF HYDROINFORMATICS, 2007, 9 (01) :39-50
[3]   Topological patterns in street networks of self-organized urban settlements [J].
Buhl, J. ;
Gautrais, J. ;
Reeves, N. ;
Sole, R. V. ;
Valverde, S. ;
Kuntz, P. ;
Theraulaz, G. .
EUROPEAN PHYSICAL JOURNAL B, 2006, 49 (04) :513-522
[4]  
Butler D., 2000, Leakage detection and management
[5]  
Clauset A, 2004, PHYS REV E, V70, DOI 10.1103/PhysRevE.70.066111
[6]   Experiments with fluid friction in roughened pipes [J].
Colebrook, CF ;
White, CM .
PROCEEDINGS OF THE ROYAL SOCIETY OF LONDON SERIES A-MATHEMATICAL AND PHYSICAL SCIENCES, 1937, 161 (A906) :367-381
[7]   Optimal Placement of isolation Valves in Water Distribution Systems Based on Valve Cost and Weighted Average Demand Shortfall [J].
Creaco, Enrico ;
Franchini, Marco ;
Alvisi, Stefano .
WATER RESOURCES MANAGEMENT, 2010, 24 (15) :4317-4338
[8]  
Darcy H., 1858, RECHERCHES RELATIVES
[9]  
Di Nardo A., 2011, P 11 INT C COMP CONT, P841
[10]   A heuristic design support methodology based on graph theory for district metering of water supply networks [J].
Di Nardo, Armando ;
Di Natale, Michele .
ENGINEERING OPTIMIZATION, 2011, 43 (02) :193-211