Watthour meter accuracy under controlled unbalanced harmonic voltage and current conditions

被引:17
作者
Domijan, A [1 ]
EmbrizSantander, E [1 ]
Gilani, A [1 ]
Lamer, G [1 ]
Stiles, C [1 ]
Williams, CW [1 ]
机构
[1] FLORIDA POWER CORP,ST PETERSBURG,FL 33711
关键词
watthour meter; harmonics; power quality; unbalance; field monitoring; testing; waveform reproduction;
D O I
10.1109/61.484002
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This work presents the results of phase I of the project on the accuracy of watthour meters when subjected to closely-duplicated real-world unbalanced harmonic voltage and current conditions. Such real-world conditions involved differences in voltage and current magnitudes as well as differences in the voltage and current total harmonic distortion levels of each phase. Tests were performed on a selected sample of nine three-phase and three single-phase watthour meters. Some results showed that under a particular set of unbalanced waveforms with harmonic conditions of I-THD > 80% and V-THD > 2%, the percentage errors exhibited by these meters ranged from -10.09% to +0.52%.
引用
收藏
页码:64 / 72
页数:9
相关论文
共 19 条