Compliance Analysis of PMU Algorithms and Devices for Wide-Area Stabilizing Control of Large Power Systems

被引:95
作者
Kamwa, Innocent [1 ]
Samantaray, S. R. [2 ]
Joos, Geza [3 ]
机构
[1] Hydro Quebec IREQ, Varennes, PQ J3X 1S1, Canada
[2] Indian Inst Technol, Sch Elect Sci, Bhubaneswar 751013, Orissa, India
[3] McGill Univ, Dept Elect & Comp Engn, Montreal, PQ H3A 2A7, Canada
关键词
Adaptive complex bandpass filtering; changing harmonics; IEEE Std. C371181-2011; Kalman filtering; phasor measurement unit (PMU); power system oscillations; synchrophasor; wide-area measurement systems (WAMS); wide-area protection and control (WAPC); FREQUENCY-MEASUREMENT; PHASOR; PERFORMANCE; TRACKING;
D O I
10.1109/TPWRS.2012.2221168
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
For the first time, IEEE Std. C37.118.1-2011 now provides metrics for PMU dynamic performance in terms of classes P and M filter designs. This paper attempts to determine whether fulfilling these requirements makes the PMU inherently well suited for stability control applications such as wide-area power system stabilizers (PSSs). In this aim, we considered two different frequency-adaptive approaches for class-P and -M compliance to ensure operation over a wide frequency range. The first is based on a finite-impulse response (FIR) with no overshoot in either the phase or the amplitude step responses, while the second is Kalman filter-based (EKF), which allows for a more refined out-of-band interference rejection at the cost of a phase step response with overshoot. These two approaches are benchmarked against Hydro-Quebec's existing PSS requirements and the conclusion is that the total vector error-based response time is not indicative of the phase lag within the frequency band of interest, nor of the 3-dB bandwidth under sinusoidal amplitude/frequency modulation phenomena, which are key criteria when specifying PSS PMUs. Using simulated and field-recorded network fault responses, we also show that a class-M PMU is unsatisfactory for wide-area stabilizing control, unless its performance is improved during the fault period, which is not covered by Std. C37.118.1-2011.
引用
收藏
页码:1766 / 1778
页数:13
相关论文
共 38 条
[21]   ACCURATE VOLTAGE PHASOR MEASUREMENT IN A SERIES-COMPENSATED NETWORK [J].
LAMBERT, J ;
PHADKE, AG ;
MCNABB, D .
IEEE TRANSACTIONS ON POWER DELIVERY, 1994, 9 (01) :501-507
[22]  
Lira R., 2011, P 17 POW SYST COMP C, P22
[23]  
Lixia M, 2010, IEEE IMTC P
[24]  
Lyons R. G., 2011, Understanding Digital Signal Processing, V3rd
[25]   An Adaptive Dynamic Phasor Estimator Considering DC Offset for PMU Applications [J].
Mai, Rui Kun ;
Fu, Ling ;
Dong, Zhao Yang ;
Kirby, Brian ;
Bo, Zhi Qian .
IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (03) :1744-1754
[26]  
Maun J. C., 2009, INT J ELEC POWER, P1
[27]  
Paolone M., 2012, P 17 POW SYST COMP C
[28]  
Peng Liu, 2009, 2009 Conference on Lasers & Electro Optics & The Pacific Rim Conference on Lasers and Electro-Optics (CLEO/PACIFIC RIM), DOI 10.1109/CLEOPR.2009.5292203
[29]   Synchronized Phasor and Frequency Measurement Under Transient Conditions [J].
Phadke, A. G. ;
Kasztenny, Bogdan .
IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (01) :89-95
[30]  
PMU System Testing and Calibration Guide, 2007, NASPI REP PERF STAND