Compliance Analysis of PMU Algorithms and Devices for Wide-Area Stabilizing Control of Large Power Systems

被引:93
作者
Kamwa, Innocent [1 ]
Samantaray, S. R. [2 ]
Joos, Geza [3 ]
机构
[1] Hydro Quebec IREQ, Varennes, PQ J3X 1S1, Canada
[2] Indian Inst Technol, Sch Elect Sci, Bhubaneswar 751013, Orissa, India
[3] McGill Univ, Dept Elect & Comp Engn, Montreal, PQ H3A 2A7, Canada
关键词
Adaptive complex bandpass filtering; changing harmonics; IEEE Std. C371181-2011; Kalman filtering; phasor measurement unit (PMU); power system oscillations; synchrophasor; wide-area measurement systems (WAMS); wide-area protection and control (WAPC); FREQUENCY-MEASUREMENT; PHASOR; PERFORMANCE; TRACKING;
D O I
10.1109/TPWRS.2012.2221168
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
For the first time, IEEE Std. C37.118.1-2011 now provides metrics for PMU dynamic performance in terms of classes P and M filter designs. This paper attempts to determine whether fulfilling these requirements makes the PMU inherently well suited for stability control applications such as wide-area power system stabilizers (PSSs). In this aim, we considered two different frequency-adaptive approaches for class-P and -M compliance to ensure operation over a wide frequency range. The first is based on a finite-impulse response (FIR) with no overshoot in either the phase or the amplitude step responses, while the second is Kalman filter-based (EKF), which allows for a more refined out-of-band interference rejection at the cost of a phase step response with overshoot. These two approaches are benchmarked against Hydro-Quebec's existing PSS requirements and the conclusion is that the total vector error-based response time is not indicative of the phase lag within the frequency band of interest, nor of the 3-dB bandwidth under sinusoidal amplitude/frequency modulation phenomena, which are key criteria when specifying PSS PMUs. Using simulated and field-recorded network fault responses, we also show that a class-M PMU is unsatisfactory for wide-area stabilizing control, unless its performance is improved during the fault period, which is not covered by Std. C37.118.1-2011.
引用
收藏
页码:1766 / 1778
页数:13
相关论文
共 38 条
[1]   An Adaptive Algorithm for Real-Time Multi-Tone Estimation and Frequency Tracking of Non-Stationary Signals [J].
Alves, D. ;
Coelho, R. .
IEEE TRANSACTIONS ON NUCLEAR SCIENCE, 2011, 58 (04) :1582-1587
[2]  
[Anonymous], 2011, THESIS
[3]  
[Anonymous], 2011, C371181TM2011 IEEE, V28
[4]   A 735 kV shunt reactors automatic switching system for Hydro-Quebec network [J].
Bernard, S ;
Trudel, G ;
Scott, G .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1996, 11 (04) :2024-2030
[5]   A KALMAN FILTERING APPROACH TO SHORT-TIME FOURIER-ANALYSIS [J].
BITMEAD, RR ;
TSOI, AC ;
PARKER, PJ .
IEEE TRANSACTIONS ON ACOUSTICS SPEECH AND SIGNAL PROCESSING, 1986, 34 (06) :1493-1501
[6]  
Castello P., 2011, 2011 IEEE 2nd International Workshop on Applied Measurements for Power Systems (AMPS 2011), P25, DOI 10.1109/AMPS.2011.6090351
[7]  
Coté P, 2001, 2001 POWER ENGINEERING SOCIETY SUMMER MEETING, VOLS 1-3, CONFERENCE PROCEEDINGS, P818, DOI 10.1109/PESS.2001.970157
[8]   MEASUREMENT OF VOLTAGE PHASE FOR THE FRENCH FUTURE DEFENSE PLAN AGAINST LOSSES OF SYNCHRONISM [J].
DENYS, P ;
COUNAN, C ;
HOSSENLOPP, L ;
HOLWECK, C .
IEEE TRANSACTIONS ON POWER DELIVERY, 1992, 7 (01) :62-69
[9]  
Faris T., 2007, 16852 PNNL PHAS MEAS
[10]  
Goldstein A., 2011, PMU MOD C37 1181 NAS