On the Temperature Measurement Bias and Time Response of an Aspirated Thermocouple in Fire Environment

被引:11
作者
Kim, Sung Chan [1 ]
Hamins, Anthony [2 ]
机构
[1] Kyungil Univ, Sch Fire & Disaster Prevent, Kyungbuk 712701, South Korea
[2] NIST, Bldg & Fire Res Lab, Gaithersburg, MD 20899 USA
关键词
temperature measurement; aspirated thermocouple; fire test; CFD;
D O I
10.1177/0734904108093516
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
To examine the uncertainty of thermocouple temperature measurements, the present study uses numerical simulations and analytical solutions to investigate the heat transfer processes associated with double shield aspirated thermocouple. This study is divided into two parts. First, 3D CFD calculations for real geometries are performed to understand the flow characteristics of double shielded aspirated thermocouples. Based on iso-thermal flow calculations for real geometry, conjugate heat transfer calculations for a 3D simplified geometry are performed to investigate the thermocouple radiative exchange errors that may be important in a fire environment. The results of the 3D heat transfer calculation are compared with algebraic solutions from a previously developed simple energy balance model and the algebraic model shows acceptable results compared to the 3D CFD model, despite its many assumptions and idealizations. A parametric study was conducted to quantify the thermocouple errors for various gas temperature and surrounding conditions. In this manner, the present study improves our understanding of the uncertainty of thermocouple temperature measurements.
引用
收藏
页码:509 / 529
页数:21
相关论文
共 14 条
[1]  
Akers A., 2006, HYDRAULIC POWER SYST
[2]  
[Anonymous], 1999, P 33 NAT HEAT TRANSF
[3]   Modeling of bare and aspirated thermocouples in compartment fires [J].
Blevins, LG ;
Pitts, WM .
FIRE SAFETY JOURNAL, 1999, 33 (04) :239-259
[4]   A two-thermocouples probe for radiation corrections of measured temperatures in compartment fires [J].
Brohez, S ;
Delvosalle, C ;
Marlair, G .
FIRE SAFETY JOURNAL, 2004, 39 (05) :399-411
[5]  
*FLUENT INC, 2003, FLUENT 6 0 US GUID
[6]  
*FLUENT INC, 2001, FLUENT 6 0 US GUID
[7]  
GLAWE GE, 1953, TN3766 NACA
[8]  
HAMINS A, 2005, 15E NIST NCSTAR
[9]  
LAUNDER BE, 1974, COMPUT METHODS APPL, V3, P289
[10]  
NEWMAN JS, 1979, J FIRE FLAMMABILITY, V10, P327