Life-Cycle Optimization of a Chiller Plant with Quantified Analysis of Uncertainty and Reliability in Commercial Buildings

被引:9
作者
Yan, Chengchu [1 ]
Cheng, Qi [2 ]
Cai, Hao [1 ]
机构
[1] Nanjing Tech Univ, Coll Urban Construct, Nanjing 210009, Jiangsu, Peoples R China
[2] Shenzhen Secom Technol Co Ltd, Shenzhen 518055, Peoples R China
来源
APPLIED SCIENCES-BASEL | 2019年 / 9卷 / 08期
基金
中国国家自然科学基金;
关键词
life-cycle; building energy efficiency; optimal design; uncertainty; reliability; chiller plant; ROBUST OPTIMAL-DESIGN; HEAT-PUMP SYSTEM; HVAC SYSTEM; SENSITIVITY-ANALYSIS; ENERGY; PERFORMANCE; EFFICIENCY;
D O I
10.3390/app9081548
中图分类号
O6 [化学];
学科分类号
0703 ;
摘要
Featured Application Proper design of a chiller plant is considered as one of the most effective ways to reduce the energy consumption of commercial buildings. Due to the improper treatment of uncertainty and reliability, existing design methods in practice often result in oversized systems. This paper proposes a design optimization method for chiller plants based on life-cycle total cost minimization with quantified analysis of uncertainty and reliability. It can ensure a chiller plant operates at its high efficient region under various cooling load conditions and provide sufficient cooling capacity even some equipment/systems with failures. Abstract Conventional and most optimal design methods for chiller plants often address the annual cooling load distribution of buildings and their peak cooling loads based on typical meteorological year (TMY) data, while the peak cooling load only appears a few times during the life-cycle and the sized chiller plant usually operates within its low efficient region. In this paper, a robust optimal design method based on life-cycle total cost was employed to optimize the design of a chiller plant with quantified analysis of uncertainty and reliability. By using the proposed design method, the optimized chiller plant can operate at its highly efficient region under various cooling load conditions, and provide sufficient cooling capacity even alongside some equipment/systems with failures. The minimum life-cycle total cost, which consists of the capital cost, operation, and availability-risk cost, can be achieved through optimizing the total cooling capacity and the numbers/sizes of chillers. A case study was conducted to illustrate the detailed implementation process of the proposed method. The performance of this design method was evaluated by comparing with that of other design methods.
引用
收藏
页数:18
相关论文
共 45 条
[31]   The reliability of technological systems with high energy efficiency in residential buildings [J].
Peruzzi, L. ;
Salata, F. ;
Vollaro, A. de Lieto ;
Vollaro, R. de Lieto .
ENERGY AND BUILDINGS, 2014, 68 :19-24
[32]   VARIATION OF ENERGY-CONSUMPTION IN DWELLINGS DUE TO CLIMATE, BUILDING AND INHABITANTS [J].
PETTERSEN, TD .
ENERGY AND BUILDINGS, 1994, 21 (03) :209-218
[33]  
Rudoy W., 1979, COOLING HEATING LOAD
[34]   Analysis of a combined cooling, heating, and power system model under different operating strategies with input and model data uncertainty [J].
Smith, Aaron ;
Luck, Rogelio ;
Mago, Pedro J. .
ENERGY AND BUILDINGS, 2010, 42 (11) :2231-2240
[35]  
Stanford HW, 2012, MECH ENG SER TXB REF, P1
[36]  
Stapelberg R.F., 2009, HDB RELIABILITY AVAI
[37]   In situ performance comparison and evaluation of three chiller sequencing control strategies in a super high-rise building [J].
Sun, Yongjun ;
Wang, Shengwei ;
Xiao, Fu .
ENERGY AND BUILDINGS, 2013, 61 :333-343
[38]   Exploring HVAC system sizing under uncertainty [J].
Sun, Yuming ;
Gu, Li ;
Wu, C. F. Jeff ;
Augenbroe, Godfried .
ENERGY AND BUILDINGS, 2014, 81 :243-252
[39]   Cost estimation and energy price forecasts for economic evaluation of retrofit projects [J].
Taal, M ;
Bulatov, I ;
Klemes, J ;
Stehlík, P .
APPLIED THERMAL ENGINEERING, 2003, 23 (14) :1819-1835
[40]  
TRNSYS, 2004, TRNSYS 16 DOC