Distance relay over-reaching due to installation of TCSC on next line

被引:3
作者
Jamali, S.
Kazemi, A.
Shateri, H.
机构
来源
2006 IEEE INTERNATIONAL SYMPOSIUM ON INDUSTRIAL ELECTRONICS, VOLS 1-7 | 2006年
关键词
D O I
10.1109/ISIE.2006.295872
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
This paper discusses the distance relay overreaching in the case of installation of Thyristor Controlled Series Compensator (TCSC) which is categorized as a series connected Flexible Alternating Current Transmission System (FACTS) device. This is done by presenting the measured impedance at the relaying point in the case of TCSC presence at the near end of the next line. Distance relay tripping characteristic is greatly influenced in the presence of TCSC on the transmission line or even in the case of installation of TCSC on the near end of the next line. Distance relay tripping characteristic depends on many factors including the power system structural conditions and the pre-fault loading, the ground fault resistance, and the TCSC compensation degree.
引用
收藏
页码:1954 / 1959
页数:6
相关论文
共 8 条
  • [1] Dommel H. W., 1997, EMPT REFERENCE MANUA
  • [2] Operation of impedance protection relays with the STATCOM
    El-Arroudi, K
    Joos, G
    McGillis, DT
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2002, 17 (02) : 381 - 387
  • [3] Jamali S, 2001, IEE CONF PUBL, P149, DOI 10.1049/cp:20010122
  • [4] JOHNS AT, 1999, FLEXIBLE AC TRANSMIS
  • [5] KHEDERZADEH M, P 2002 IEEE C EXH TR, V3, P2043
  • [6] Wang WG, 1998, POWERCON '98: 1998 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY - PROCEEDINGS, VOLS 1 AND 2, P382, DOI 10.1109/ICPST.1998.728991
  • [7] XIA YQ, 1994, IEEE T POWER DELIVER, V9, P480, DOI 10.1109/61.277720
  • [8] AN ADAPTIVE APPROACH IN DIGITAL DISTANCE PROTECTION
    ZHANG, ZZ
    CHEN, DS
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1991, 6 (01) : 135 - 142