Optimization of capacity and operation for CCHP system by genetic algorithm

被引:357
作者
Wang, Jiang-Jiang [1 ]
Jing, You-Yin [1 ]
Zhang, Chun-Fa [1 ]
机构
[1] N China Elect Power Univ, Sch Energy & Power Engn, Baoding 071003, Hebei Province, Peoples R China
关键词
Combined cooling heating and power (CCHP) system; Optimization; Capacity; Operation strategy; Genetic algorithm (GA); OPTIMAL-DESIGN; TRIGENERATION SYSTEMS; GENERATION SYSTEMS; PROGRAMMING-MODEL; ENERGY-SYSTEMS; POWER; COGENERATION; PERFORMANCE; PLANTS;
D O I
10.1016/j.apenergy.2009.08.005
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The technical, economical and environmental performances of combined cooling, heating and power (CCHP) system are closely dependent on its design and operation strategy. This paper analyzes the energy flow of CCHP system and deduces the primary energy consumption following the thermal demand of building. Three criteria, primary energy saving (PES). annual total cost saving (ATCS), and carbon dioxide emission reduction (CDER) are selected to evaluate the performance of CCHP system. Based on the energy flow of CCHP system, the capacity and operation of CHP system are optimized by genetic algorithm (GA) so as to maximize the technical, economical and environmental benefits achieved by CCHP system in comparison to separation production system. A numerical example of gas CCHP system for a hotel building in Beijing is given to ascertain the effectiveness of the optimal method. Furthermore, a sensitivity analysis is presented in order to show how the optimal operation strategy would vary due to the changes of electricity price and gas price. (C) 2009 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1325 / 1335
页数:11
相关论文
共 39 条
  • [1] Design optimization of composite laminated structures using genetic algorithms and finite element analysis
    Almeida, F. S.
    Awruch, A. M.
    [J]. COMPOSITE STRUCTURES, 2009, 88 (03) : 443 - 454
  • [2] [Anonymous], 2006, BUILDING ENV SYSTEM
  • [3] A mixed integer programming model for optimal design of trigeneration in a hospital complex
    Arcuri, P.
    Florio, G.
    Fragiacomo, P.
    [J]. ENERGY, 2007, 32 (08) : 1430 - 1447
  • [4] Simulation and optimization of the performance in the air-conditioning season of a BCHP system in China
    Cao, Jia-cong
    Liu, Feng-qiang
    [J]. ENERGY AND BUILDINGS, 2008, 40 (03) : 185 - 192
  • [5] Optimal design of CHCP plants in the civil sector by thermoeconomics
    Cardona, E.
    Piacentino, A.
    [J]. APPLIED ENERGY, 2007, 84 (7-8) : 729 - 748
  • [6] A methodology for sizing a trigeneration plant in mediterranean areas
    Cardona, E
    Piacentino, A
    [J]. APPLIED THERMAL ENGINEERING, 2003, 23 (13) : 1665 - 1680
  • [7] Assessment of the greenhouse gas emissions from cogeneration and trigeneration systems. Part I: Models and indicators
    Chicco, Gianfranco
    Mancarella, Pierluigi
    [J]. ENERGY, 2008, 33 (03) : 410 - 417
  • [8] Distributed multi-generation: A comprehensive view
    Chicco, Gianfranco
    Mancarefla, Pierluigi
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2009, 13 (03) : 535 - 551
  • [9] Cost-optimized real-time operation of CHP systems
    Cho, Heejin
    Luck, Rogelio
    Eksioglu, Sandra D.
    Chamra, Louay M.
    [J]. ENERGY AND BUILDINGS, 2009, 41 (04) : 445 - 451
  • [10] Exergy analysis, parametric analysis and optimization for a novel combined power and ejector refrigeration cycle
    Dai, Yiping
    Wang, Jiangfeng
    Gao, Lin
    [J]. APPLIED THERMAL ENGINEERING, 2009, 29 (10) : 1983 - 1990