Experimental study on smoke temperature distribution under different power conditions in utility tunnel

被引:32
作者
Zhao, Yong-chang [1 ,2 ,3 ]
Zhu, Guo-qing [1 ,2 ,3 ]
Gao, Yun-ji [1 ,2 ,3 ]
机构
[1] China Univ Min & Technol, Sch Safety Engn, Xuzhou 221116, Jiangsu, Peoples R China
[2] China Univ Min & Technol, Key Lab Gas & Fire Control Coal Mines, Xuzhou 221116, Jiangsu, Peoples R China
[3] China Univ Min & Technol, Fire Res inst, Xuzhou 221116, Jiangsu, Peoples R China
基金
国家重点研发计划;
关键词
Experiment; Temperature distribution; Utility tunnel; Tunnel fire; Pool fire; LONGITUDINAL VENTILATION; NEAR-FIELD; FIRE; FLOW; SIMULATION;
D O I
10.1016/j.csite.2018.03.002
中图分类号
O414.1 [热力学];
学科分类号
摘要
The longitudinal and cross-sectional temperature distributions are measured in reduced-scale tunnel fire experiments with different fire power conditions. Field tests are carried out in a utility tunnel with pool fires. The experiments studied the ceiling temperature along the tunnel centerline, the vertical temperature below the ceiling and the temperature in the direction of radian in the same section with the fire source. The results from the burning experiments are analyzed. The longitudinal temperature distribution along the tunnel can be fairly well fitted by exponential equations. And the thermal radiation of the smoke layer has a significant effect on the temperature below the ceiling. In addition, in the direction of tunnel radian, the temperature growth rate of the region above 45 degrees are obviously faster and the temperature is higher. Therefore, to shorten the response time of the detector to the fire, it is desirable to place the heat and smoke detectors at the top of the utility tunnel.
引用
收藏
页码:69 / 76
页数:8
相关论文
共 18 条
[1]  
[Anonymous], 2012, THESIS
[2]  
[Anonymous], 2006, THESIS
[3]  
Bailey JL, 2002, FIRE PROTECT ENG, V12, P139
[4]   Experimental and numerical study of fire in a midscale test tunnel [J].
Blanchard, E. ;
Boulet, P. ;
Desanghere, S. ;
Cesmat, E. ;
Meyrand, R. ;
Garo, J. P. ;
Vantelon, J. P. .
FIRE SAFETY JOURNAL, 2012, 47 :18-31
[5]  
Brahim K, 2013, J APPL FLUID MECH, V6, P49
[6]   Experimental investigation of pool fire behavior to different tunnel-end ventilation opening areas by sealing [J].
Chen, Chang-kun ;
Xiao, Huang ;
Wang, Nan-nan ;
Shi, Cong-ling ;
Zhu, Cong-xiang ;
Liu, Xuan-ya .
TUNNELLING AND UNDERGROUND SPACE TECHNOLOGY, 2017, 63 :106-117
[7]   THE FLOW OF FIRE GASES UNDER A BEAMED CEILING [J].
DELICHATSIOS, MA .
COMBUSTION AND FLAME, 1981, 43 (01) :1-10
[8]  
Evers E, 1978, BUILD RES ESTABLISH, P69
[9]   Effect of tunnel cross section on gas temperatures and heat fluxes in case of large heat release rate [J].
Fan, Chuan Gang ;
Li, Ying Zhen ;
Ingason, Haukur ;
Lonnermark, Anders .
APPLIED THERMAL ENGINEERING, 2016, 93 :405-415
[10]  
GB, GB 50838-2015