A Single-ended Transient Based Voltage Protection Method of UHVDC Transmission Line Which Distinguishes the Opposite Side's Internal and External Fault with Protectors

被引:0
|
作者
Chen, Shilong [1 ]
Zhang, Jie [1 ]
Xie, Jiawei [1 ]
Liu, Li [1 ]
机构
[1] Kunming Univ Sci & Technol, Sch Elect Power Engn, Kunming 650500, Yunnan Province, Peoples R China
关键词
Physical boundary of UHVDC transmission line; Frequency characteristic; Fault-generated signal; Attenuation; Simulation; PSCAD;
D O I
10.4028/www.scientific.net/AMM.291-294.2244
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The paper studied the frequency characteristics of UHVDC transmission line and UHVDC transmission line boundary and their attenuation to high frequency components of fault-generated transient signal. The paper points out that existing approaches which utilize protectors to distinguish local side's internal or external fault can't protect the whole line. UHVDC transmission line and UHVDC transmission line boundary's attenuation to high frequency fault-generated transient signal is overall considered, and a single-ended transient based voltage protection method which distinguishes the opposite side's internal and external fault is proposed. The Yunnan-Guangdong UHVDC model of actual parameters was built up by PSCAD, and simulation experiment was conducted.
引用
收藏
页码:2244 / 2249
页数:6
相关论文
共 21 条
  • [1] A single-ended current direction transient protection of UHVDC transmission line
    Chen, Shilong
    Zhang, Jie
    Liu, Hongrui
    Xie, Jiawei
    Hou, Yunchuan
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2016, 31 (02): : 171 - 177
  • [2] Single-ended protection method for hybrid HVDC transmission line based on transient voltage characteristic frequency band
    Shu, Hongchun
    Wang, Shixin
    Lei, Shunguang
    PROTECTION AND CONTROL OF MODERN POWER SYSTEMS, 2023, 8 (01)
  • [3] Single-ended protection method for hybrid HVDC transmission line based on transient voltage characteristic frequency band
    Hongchun Shu
    Shixin Wang
    Shunguang Lei
    Protection and Control of Modern Power Systems, 2023, 8
  • [4] Single-Ended Protection Method for UHVDC Transmission Line Based on Hilbert Energy Amplitude Information and Waveform Information
    Fan Y.
    Wang Y.
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2021, 36 (09): : 1818 - 1830
  • [5] Single-ended protection method of double-ended weak-infeed AC tie-line based on opposite-side voltage consistency analysis
    Li, Botong
    Li, Jianing
    Wang, Shuai
    Chen, Xiaolong
    Dong, Yuejin
    ENERGY REPORTS, 2024, 12 : 1109 - 1120
  • [6] A parameter modification based transmission line fault location method using single-ended current
    Liu, Yuping
    He, Zhengyou
    He, Wen
    2012 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2012,
  • [7] MMC-HVDC line fault identification scheme based on single-ended transient voltage information entropy
    Shu, Hongchun
    Wang, Guangxue
    Tian, Xincui
    Ju, Xiayang
    An, Na
    Bo, Zhiqian
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2022, 141
  • [8] A novel distance protection scheme using single-ended transient voltage based on generalized S transform
    Li, Yifan
    Sun, Peng
    Li, Hui
    Huang, Shaofeng
    Wu, Haifeng
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2022, 16 (22) : 4652 - 4661
  • [9] Single-ended protection method of MMC-HVDC transmission line based on random matrix theory
    Shu, Hongchun
    Wang, Guangxue
    Tian, Xincui
    Lei, Shunguang
    Jiang, Xiaohan
    Bo, Zhiqian
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2022, 142
  • [10] Single-ended Protection Method of Flexible DC Line Based on Extremum Time of Fault Forward Traveling Wave
    Chen M.
    Jia K.
    Yao K.
    Liu X.
    Wen Z.
    Bi T.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2023, 43 (10): : 3742 - 3757