Application Condition of 40.5kV Air Insulated Metal Enclosed Switchgear with VCB in China

被引:0
作者
Li, Hongmei [1 ]
Tan, Dongxian [2 ]
Liu, Yuhua [3 ]
机构
[1] Shanghai Ocean Univ Engn Sci & Technol, Shanghai, Peoples R China
[2] Shanghai ROX Elect Appliance Co Ltd, Shanghai, Peoples R China
[3] Jiangsu Dongtai Elect Power Co, Nantong, Peoples R China
来源
2012 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED) | 2012年
关键词
Switchgear; Air Insulated; Insulation fault and failure; Simulation; Electrical test;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In the advantage of high reliability, environment friendly and maintenance-free, VCB has possessed the large-scale market capacity in China and other countries in worldwide. At the same time, compact 40.5kV air insulated switchgear with VCB is mostly used in power substation of 220kV and industry consumer with heavy loads. Practical operation of many years has proved that many faults will occur in 40.5kV air insulated metal enclosed switchgear. Statistic date shows the most fault and failure is resulted due to the poor insulation performance. Based on the different appearance of fault and failure occurred in the operation field of switchgear, the root cause which results in insulation fault and failure were investigated in this paper, through simulation and electrical test. Detail analysis on fault and failure show that there are a lot of factors which can lead to the different faults and failure mode. Some key cause can be deduced as following: selection of insulation part and material, design of insulation parts, manufacture processing of insulation parts, assembly processing of components used in air insulated switchgear, filed environment and switchgear maintenance. For improve the insulation performance of air insulated metal enclosed switchgear, some FEA simulation and electrical tests were implemented in this paper, test results prove that simulation is a useful tool to optimize the quality of insulation parts.
引用
收藏
页数:4
相关论文
共 6 条
  • [1] Analysis on Failure causes of bushing used in 40.5kV metal enclosed air insulation switchgear
    Tan, Dongxian
    Li, Hongmei
    Xiao, Dengming
    2014 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2014,
  • [2] Numerical analysis and application of electric field grading device for metal-enclosed switchgear
    Serdal Arslan
    Yunus Bicen
    Ömür Binarbasi
    SN Applied Sciences, 2021, 3
  • [3] Numerical analysis and application of electric field grading device for metal-enclosed switchgear
    Arslan, Serdal
    Bicen, Yunus
    Binarbasi, Omur
    SN APPLIED SCIENCES, 2021, 3 (02):
  • [4] Limitations in the Application of Computer Simulations of Temperature Rise of Completely New Designs of MV Metal Enclosed Switchgear
    Fjeld, Elin
    Pedersen, Atle
    Kriegel, Martin
    Singh, Shailendra
    Barrio, Sergio
    Snajdr, Jaroslav
    Li, ZuHui
    IEEE TRANSACTIONS ON POWER DELIVERY, 2021, 36 (05) : 2740 - 2747
  • [5] Through-Process Finite Element Modeling for Warm Flanging Process of Large-Diameter Aluminum Alloy Shell of Gas Insulated (Metal-Enclosed) Switchgear
    Zhang, Da-Wei
    Shi, Tian-Lin
    Zhao, Sheng-Dun
    MATERIALS, 2019, 12 (11)
  • [6] Application Experience of SF6 -Free 72.5kV Hybrid-Gas-Insulated-Switchgears in China
    Liu, Yitao
    Hong, He
    Lu, Xucheng
    Li, Shuang
    Hou, Yaping
    Zhang, Jun
    Liu, Guangfu
    Zhang, Jiaosuo
    2017 4TH INTERNATIONAL CONFERENCE ON ELECTRIC POWER EQUIPMENT-SWITCHING TECHNOLOGY (ICEPE-ST), 2017, : 272 - 274