Experimental study of perforated suspended ceilings as diffuse ventilation air inlets

被引:42
作者
Hviid, Christian Anker [1 ,2 ]
Svendsen, Svend [1 ]
机构
[1] Tech Univ Denmark, Dept Civil Engn, DK-2800 Lyngby, Denmark
[2] ALECTIA AS, DK-2830 Virum, Denmark
关键词
Comfort ventilation; Diffuse ventilation; Low-impulse ventilation; Ventilation effectiveness; Thermal comfort; Experiments; Tracer-gas; DISPLACEMENT VENTILATION; MIXING VENTILATION; TERMINAL DEVICES; QUALITY; ROOMS;
D O I
10.1016/j.enbuild.2012.09.010
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
An experimental study is reported in this paper for a diffuse ceiling ventilation concept. The analyses were carried out with two different porous surfaces mounted in a suspended ceiling: perforated tiles of aluminium and of gypsum. Ventilation air was supplied above the suspended ceiling effectively creating a plenum for air distribution. The experiments were carried out in a climatic chamber and documented an air change efficiency equal to fully mixed conditions with a pressure drop of 0.5-1.5 Pa and with no evidence of thermal discomfort. The magnitude of the pressure drop was enough to sustain the pressure of the plenum and ensure uni-directional airflow through the ceiling. Consequently only reverse flow of insignificant magnitude was observed which has a positive impact on the hygiene of the plenum. Furthermore, the measurements documented that the ceiling acts as a radiant cooling surface which increases the potential and applicability of the concept. Risk of thermal discomfort was not disclosed but the study did show evidence of large fluctuating air movements which could stem from transient behaviour creating sensations of draught to the occupants. (C) 2012 Elsevier B.V. All rights reserved.
引用
收藏
页码:160 / 168
页数:9
相关论文
共 25 条
[1]  
[Anonymous], 2007, 15251 EN EUR COMM ST
[2]  
[Anonymous], 1986, HDB KLIMATECHNIK, V2
[3]  
[Anonymous], 1998, 17521 CR CEN EUR COM
[4]  
[Anonymous], 2009, SOUNDTEX AC NONW
[5]  
Awbi H., 2008, Ventilation of Buildings
[6]   Indoor air quality in rooms with cooled ceilings. Mixing ventilation or rather displacement ventilation? [J].
Behne, M .
ENERGY AND BUILDINGS, 1999, 30 (02) :155-166
[7]   Experimental and numerical analysis of air and radiant cooling systems in offices [J].
Corgnati, S. P. ;
Perino, M. ;
Fracastoro, G. V. ;
Nielsen, P. V. .
BUILDING AND ENVIRONMENT, 2009, 44 (04) :801-806
[8]  
Elmroth A., 1996, OPTIMA HOUSE AIR QUA
[9]   HYDRONIC RADIANT COOLING - PRELIMINARY ASSESSMENT [J].
FEUSTEL, HE ;
STETIU, C .
ENERGY AND BUILDINGS, 1995, 22 (03) :193-205
[10]  
Jacobs P., 2008, P IND AIR COP DENM