CT Saturation Detection Based on the Distance Between Consecutive Points in the Plans Formed by the Secondary Current Samples and Their Difference-Functions

被引:23
作者
dos Santos, E. M. [1 ]
Cardoso, G., Jr. [2 ]
Farias, P. E. [3 ]
de Morais, A. P. [4 ]
机构
[1] Fed Univ Pampa UNIPAMPA, Ctr Technol, Alegrete Dept, BR-97546550 Algrete, Brazil
[2] Fed Univ Santa Maria UFSM, Electromech & Power Syst Dept, BR-97105900 Santa Maria, RS, Brazil
[3] Elect Energy Proc Dept, BR-97105900 Santa Maria, RS, Brazil
[4] Ind Tech Sch Santa Maria CTISM, Electrotech Dept, BR-97105900 Santa Maria, RS, Brazil
关键词
Current transformer (CT); detection; protection; relays; saturation; COMPENSATION; TRANSIENT;
D O I
10.1109/TPWRD.2012.2220382
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper proposes a novel method to detect the saturation intervals where the secondary current of current transformers for protection purposes becomes distorted. The method is based on the analysis of plans formed by the secondary current samples and their difference-functions (del[n]). The distance between consecutive points in these plans has a significant increase when saturation occurs, bucking the trend of the intervals without saturation. Two plans are considered: del[2] versus del[1] and del[3] versus del[2]. Besides the ease of implementation, the results indicate the effectiveness of the method to detect saturation intervals.
引用
收藏
页码:29 / 37
页数:9
相关论文
共 12 条
[1]  
[Anonymous], 1995, C57131995 ANSIIEEE
[2]   Compensation of Distorted Secondary Current Caused by Saturation and Remanence in a Current Transformer [J].
Hong, Ying-Yi ;
Wei, Da-Wei .
IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (01) :47-54
[3]  
*IEEE, 2008, C371102007 IEEE
[4]   Compensation of the distortion in the secondary current caused by saturation and remanence in a CT [J].
Kang, YC ;
Lim, UJ ;
Kang, SH ;
Crossley, PA .
IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (04) :1642-1649
[5]   A CT saturation detection algorithm [J].
Kang, YC ;
Ok, SH ;
Kang, SH .
IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (01) :78-85
[6]   EXPERIMENTAL EVALUATION OF EMTP-BASED CURRENT TRANSFORMER MODELS FOR PROTECTIVE RELAY TRANSIENT STUDY [J].
KEZUNOVIC, M ;
KOJOVIC, L ;
ABUR, A ;
FROMEN, CW ;
SEVCIK, DR ;
PHILLIPS, F .
IEEE TRANSACTIONS ON POWER DELIVERY, 1994, 9 (01) :405-412
[7]   Combined wavelet transform and regression technique for secondary current compensation of current transformers [J].
Li, F ;
Li, Y ;
Aggarwal, R .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2002, 149 (04) :497-503
[8]   Morphological Lifting Scheme for Current Transformer Saturation Detection and Compensation [J].
Lu, Z. ;
Smith, J. S. ;
Wu, Q. H. .
IEEE TRANSACTIONS ON CIRCUITS AND SYSTEMS I-REGULAR PAPERS, 2008, 55 (10) :3349-3357
[9]   Current-transformer saturation detection with genetically optimized neural networks [J].
Rebizant, Waldemar ;
Bejmert, Daniel .
IEEE TRANSACTIONS ON POWER DELIVERY, 2007, 22 (02) :820-827
[10]  
Stachel P., 2009, POW EN SOC GEN M CAL