Flow patterns and plug/slug flow characteristic of R134a in a 0.643 mm microchannel tube

被引:11
作者
Li, Houpei [1 ]
Hrnjak, Pega [1 ,2 ]
机构
[1] Univ Illinois, Air Conditioning & Refrigerat Ctr, Mech Sci & Engn, 1206 West Green St, Urbana, IL 61801 USA
[2] CTS, 2209 Willow Rd, Urbana, IL USA
关键词
LIQUID 2-PHASE FLOW; HEAT-TRANSFER; PRESSURE-DROP; REVERSE FLOW; VISUALIZATION; LENGTH; SLUG;
D O I
10.1016/j.ijheatmasstransfer.2018.12.069
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper presents visualization of the two-phase flow of R134a in a 24-port microchannel tube with the average hydraulic diameter of 0.643 mm. The experiment is conducted on the same facility in the previous work for R32 (Li and Hrnjak, 2019). Mass flux covers the range from 50 to 250 kg-m(-2)s(-1). The twophase flow is generated by adding heat in several steps to originally subcooled refrigerant at the very entrance. When mass flux is 50 kg-m(-2)s(-1), no annular flow is observed in the tube. The annular flow starts at x = 0.9 when mass flux is 100 kg-m(-2)s(-1) and x = 0.6 when 250 kg-m(-2)s(-1). The transitional flow starts at x = 0.25 (G = 50 kg-m(-2)s(-1)) and x = 0.8 (250 kg-m(-2)s(-1)). Revellin and Thome (2007), Ong and Thome (2011), and Zhao and Hu (2000) correlations are plotted against the measurements. None of them fit our data since the experiment is in lower mass flux than the database of their correlations'. The interface velocity and vapor plug length fraction (close to void fraction) are measured from the high speed videos. The velocity and vapor fraction agree to results based on the homogeneous assumption. In plug/slug flow, both the vapor plug and liquid slug lengths are uneven. The length distribution of plug and slug seems to follow Beta distribution. When the quality is low, the quantity of short vapor plugs is larger than long plugs. At fixed mass flux, when quality increases, length of vapor plugs increases and length of liquid slugs decreases. (C) 2018 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1062 / 1073
页数:12
相关论文
共 19 条
[1]   A MODEL FOR SLUG LENGTH DISTRIBUTION IN GAS-LIQUID SLUG FLOW [J].
BARNEA, D ;
TAITEL, Y .
INTERNATIONAL JOURNAL OF MULTIPHASE FLOW, 1993, 19 (05) :829-838
[2]  
Field B. S., 2007, TR261 AIR COND REFR
[3]   CHARACTERISTICS OF GAS-LIQUID 2-PHASE FLOW IN A CAPILLARY-TUBE [J].
FUKANO, T ;
KARIYASAKI, A .
NUCLEAR ENGINEERING AND DESIGN, 1993, 141 (1-2) :59-68
[4]   Adiabatic gas-liquid flow in microchannels [J].
Kawaji, M ;
Chung, PMY .
MICROSCALE THERMOPHYSICAL ENGINEERING, 2004, 8 (03) :239-257
[5]  
Li H., 2016, EXPT FACILITY MICROC
[6]   Flow visualization of R32 in parallel-port microchannel tube [J].
Li, Houpei ;
Hrnjak, Pega .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2019, 128 :1-11
[7]   Heat transfer and pressure drop of R32 evaporating in one pass microchannel tube with parallel channels [J].
Li, Houpei ;
Hrnjak, Pega .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2018, 127 :526-540
[8]   Measurement of heat transfer coefficient and pressure drop during evaporation of R134a in new type facility with one pass flow through microchannel tube [J].
Li, Houpei ;
Hrnjak, Pega .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2017, 115 :502-512
[9]   Visualization and measurement of reverse flow in an actual channel of a microchannel evaporator [J].
Li, Huize ;
Hrnjak, Pega .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2017, 108 :2346-2354
[10]  
Nino V. G., 2002, Characterization of two-phase flow in microchannels