Experimental study on heat and mass transfer characteristics for a desiccant-coated fin-tube heat exchanger

被引:75
作者
Li, Zhang [1 ]
Michiyuki, Saikawa [1 ]
Takeshi, Fujinawa [1 ]
机构
[1] Cent Res Inst Elect Power Ind, Yokosuka, Kanagawa 2400196, Japan
关键词
Desiccant; Adsorption; Desorption; Heat exchanger; Heat transfer; Mass transfer; SILICA-GEL; PORE DIFFUSION; PERFORMANCE; DEHUMIDIFICATION; TRANSPORT; SURFACE; SYSTEM; WHEELS; BED;
D O I
10.1016/j.ijheatmasstransfer.2015.05.095
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this study, we investigated the heat and mass transfer characteristics of a desiccant-coated fin-tube heat exchanger (DCHE), in which the desiccant was coated on the surface of a conventional fin-tube heat exchanger. It differs from desiccant wheels in which the desiccant is cooled or heated by the fluid inside the tube during the adsorption or desorption process, and from conventional heat exchangers, in which moisture transfer occurs and the latent heat transfer is caused by phase change of the adsorbed moisture. Firstly, the heat and mass-transfer model for the DCHE was presented in this paper, whereupon the influences of air velocity, desiccant temperature and moisture content on the overall mass-transfer coefficient were separately analyzed for desorption and adsorption processes. It emerged that the overall mass-transfer coefficient rose with increasing air velocity. The moisture content of the desiccant significantly impacted on the overall mass-transfer coefficient. Higher desiccant temperature resulted in lower overall mass-transfer coefficient. Finally, the heat transfer model given in this paper was applied to calculate the DCHE heat transfer rate and the values obtained by calculation were observed to correlate well with the experimental results. (C) 2015 Elsevier Ltd. All rights reserved.
引用
收藏
页码:641 / 651
页数:11
相关论文
共 35 条
[1]   Field performance measurements of a heat pump desiccant unit in heating and humidification mode [J].
Aynur, Tolga Nurettin ;
Hwang, Yunho ;
Radermacher, Reinhard .
ENERGY AND BUILDINGS, 2010, 42 (05) :678-683
[2]  
Bird R.B., 2007, Transport Phenomena, P521
[3]   Optimization of desiccant wheel speed and area ratio of regeneration to dehumidification as a function of regeneration temperature [J].
Chung, Jae Dong ;
Lee, Dae-Young ;
Yoon, Seok Mann .
SOLAR ENERGY, 2009, 83 (05) :625-635
[4]   Water adsorption-desorption isotherms of two-dimensional hexagonal mesoporous silica around freezing point [J].
Endo, Akira ;
Yamaura, Toshio ;
Yamashita, Kyohei ;
Matsuoka, Fumio ;
Hihara, Eiji ;
Daiguji, Hirofumi .
JOURNAL OF COLLOID AND INTERFACE SCIENCE, 2012, 367 :409-414
[5]   Study of a waste heat driven modified packed desiccant bed dehumidifier [J].
Fathalah, K ;
Aly, SE .
ENERGY CONVERSION AND MANAGEMENT, 1996, 37 (04) :457-471
[6]   Experimental investigation on a solid desiccant system integrated with a R407C compression air conditioner [J].
Fatouh, M. ;
Ibrahim, Talaat A. ;
Mostafa, A. .
ENERGY CONVERSION AND MANAGEMENT, 2009, 50 (10) :2670-2679
[7]  
Fujiyi M. O., 1992, COMPACT HEAT EXCHANG, P118
[8]   A review of the mathematical models for predicting rotary desiccant wheel [J].
Ge, T. S. ;
Li, Y. ;
Wang, R. Z. ;
Dai, Y. J. .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2008, 12 (06) :1485-1528
[9]   Simulation investigation on solar powered desiccant coated heat exchanger cooling system [J].
Ge, T. S. ;
Dai, Y. J. ;
Li, Y. ;
Wang, R. Z. .
APPLIED ENERGY, 2012, 93 :532-540
[10]   Performance study of silica gel coated fin-tube heat exchanger cooling system based on a developed mathematical model [J].
Ge, T. S. ;
Dai, Y. J. ;
Wang, R. Z. .
ENERGY CONVERSION AND MANAGEMENT, 2011, 52 (06) :2329-2338