Loading of transformers in conditions of controlled cooling system

被引:13
|
作者
Radakovic, Zoran [1 ]
Jacic, Dusan [1 ]
Lukic, Jelena [2 ]
Milosavljevic, Srdjan [2 ]
机构
[1] Univ Belgrade, Fac Elect Engn, Belgrade, Serbia
[2] Inst Nikola Tesla, Belgrade, Serbia
关键词
transformer loading; fouling of transformer coolers; automatic control of transformer cooling system; monitoring of power transformer; POWER TRANSFORMERS; TEMPERATURES;
D O I
10.1002/etep.1688
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The paper deals with thermal modelling of transformers with automatic control of the cooling system. The case study was done on 725 MVA transformer with OFAF cooling, having eight compact coolers, each of them with their own pump and hysteresis control: four coolers, when top oil temperature drops below 30 degrees C, and six coolers, when top oil temperature rises above 45 degrees C. The consequence of operation with different number of coolers is change of thermal characteristics of the transformer. Additional phenomenon causing change of thermal characteristics is fouling of the coolers. These variable thermal characteristics are included in mathematical models used for the calculation of top oil and hot-spot temperatures in all applications of such calculation algorithms: protection, monitoring, estimation of overload capability, calculation of thermal ageing, etc. Copyright (c) 2012 John Wiley & Sons, Ltd.
引用
收藏
页码:203 / 214
页数:12
相关论文
共 50 条
  • [1] Transformers loading conditions for future thermally unfavorabe environments
    Hashmi, G. Murtaza
    Lehtonen, Matti
    Millar, R. John
    ECT - 2008: PROCEEDINGS OF THE 3RD INTERNATIONAL CONFERENCE ON ELECTRICAL AND CONTROL TECHNOLOGIES, 2008, : 278 - 283
  • [2] THERMODYNAMIC RESPONSE OF MY CONVERTER TRANSFORMERS UNDER CONTROLLED LOADING
    PENN, DR
    MELVOLD, DJ
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1982, 101 (05): : 1081 - 1087
  • [3] LOADING TRANSFORMERS
    CLEGG, DR
    ELECTRICAL REVIEW, 1970, 186 (12): : 426 - &
  • [4] Thermal Simulations for Optimization of Dry Transformers Cooling System
    Cremasco, Andrea
    Di Barba, Paolo
    Cranganu-Cretu, Bogdan
    Wu, Wei
    Blaszczyk, Andreas
    SCIENTIFIC COMPUTING IN ELECTRICAL ENGINEERING (SCEE 2014), 2016, 23 : 103 - 113
  • [5] CAD for Three Phase ONAN Cooling System Transformers
    Dragomir, Robert-Constantin
    Deaconu, Ioan-Dragos
    Chirila, Aurel-Ionut
    Deaconu, Anca-Simona
    Navrapescu, Valentin
    2015 9TH INTERNATIONAL SYMPOSIUM ON ADVANCED TOPICS IN ELECTRICAL ENGINEERING (ATEE), 2015, : 31 - 36
  • [7] LOADING OF POWER TRANSFORMERS
    NORRIS, ET
    PROCEEDINGS OF THE INSTITUTION OF ELECTRICAL ENGINEERS-LONDON, 1967, 114 (02): : 228 - &
  • [8] Optimisation of the cooling unit in the system for supervising the condition of large power transformers
    Wosiak, Agnieszka
    Lipinski, Piotr
    Kazmierski, Marceli
    Kersz, Igor
    PRZEGLAD ELEKTROTECHNICZNY, 2009, 85 (12): : 166 - 169
  • [9] Importance of cooling system optimization with regard to lifetime and reliability of power transformers
    Gradnik, Tim
    Babuder, Maks
    Koncan-Gradnik, Maja
    ELEKTROTEHNISKI VESTNIK-ELECTROCHEMICAL REVIEW, 2006, 73 (04): : 232 - 240
  • [10] Evaluation of the Cooling System Calculation Technique for Oil-Immersed Transformers
    Dmitrieva, O. S.
    Patrakova, G. R.
    Dmitriev, A., V
    2017 INTERNATIONAL CONFERENCE ON INDUSTRIAL ENGINEERING, APPLICATIONS AND MANUFACTURING (ICIEAM), 2017,