Dispersion of indoor air pollutants emitted at near-floor levels in rooms with floor heating and mixing ventilation

被引:7
作者
Jurelionis, Andrius [1 ]
Stasiuliene, Laura [1 ]
Prasauskas, Tadas [2 ]
Martuzevicius, Dainius [2 ]
机构
[1] Kaunas Univ Technol, Dept Bldg Energy Syst, Studentu G 48, LT-51367 Kaunas, Lithuania
[2] Kaunas Univ Technol, Dept Environm Technol, Kaunas, Lithuania
关键词
Floor heating; Indoor air pollution; Personal exposure; Air distribution; CFD predictions; PERSONAL EXPOSURE; EMISSIONS; PARTICLES; CARPETS; VOC;
D O I
10.1177/1420326X16669975
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The usage of floor heating is increasing in low-energy buildings as it enables efficient applications of low-exergy level heat sources as well as provides a uniform distribution of air temperature and low air velocities in heated spaces. The aim of this study was to analyse the effects of floor heating on the dispersion of gaseous pollutants emitted at the floor level, considering that carpets and flooring materials can be sources of such pollution. Mixing ventilation with high-level wall grille air supply and in-ceiling four-way air supply was tested numerically and experimentally in the full-scale chamber at the air change rate of 2 h(-1). Three positions of a heated dummy in relation to the pollution source, cold surface and air supply diffusers were analysed. Both experiments and CFD predictions revealed the overall positive effect of floor heating on ventilation effectiveness and personal exposure. Floor heating increased pollutant removal effectiveness by 5% and reduced personal exposure by 22% on average.
引用
收藏
页码:205 / 218
页数:14
相关论文
共 31 条
  • [1] Ala-Juusela M., 2003, HEATING COOLING FOCU
  • [2] Formaldehyde and TVOC emission behavior of laminate flooring by structure of laminate flooring and heating condition
    An, Jae-Yoon
    Kim, Sumin
    Kim, Hyun-Joong
    [J]. JOURNAL OF HAZARDOUS MATERIALS, 2011, 187 (1-3) : 44 - 51
  • [3] Boerstra A, 2000, HLTH BUILDINGS 2000
  • [4] Personal exposure in displacement ventilated rooms
    Brohus, H
    Nielsen, PV
    [J]. INDOOR AIR-INTERNATIONAL JOURNAL OF INDOOR AIR QUALITY AND CLIMATE, 1996, 6 (03): : 157 - 167
  • [5] Floor heating and cooling combined with displacement ventilation: Possibilities and limitations
    Causone, Francesco
    Baldin, Fabio
    Olesen, Bjarne W.
    Corgnati, Stefano P.
    [J]. ENERGY AND BUILDINGS, 2010, 42 (12) : 2338 - 2352
  • [6] Cermak R, 2004, ROOMVENT 2004
  • [7] EC, 2009, TS34B TOTALSEAL 34 B
  • [8] EN, 2007, EN 15251:2007
  • [9] Numerical comparison of airborne particles deposition and dispersion in radiator and floor heating systems
    Golkarfard, V.
    Talebizadeh, P.
    [J]. ADVANCED POWDER TECHNOLOGY, 2014, 25 (01) : 389 - 397
  • [10] Evaluation of emissions of total volatile organic compounds from carpets in an environmental chamber
    Guo, H
    Murray, F
    Lee, SC
    Wilkinson, S
    [J]. BUILDING AND ENVIRONMENT, 2004, 39 (02) : 179 - 187