Improved Control Strategy for DFIG Wind Turbines for Low Voltage Ride Through

被引:18
作者
Wu, Zaijun [1 ]
Zhu, Chanxia [1 ]
Hu, Minqiang [1 ]
机构
[1] Southeast Univ, Sch Elect Engn, Nanjing 210096, Jiangsu, Peoples R China
基金
国家高技术研究发展计划(863计划); 中国国家自然科学基金;
关键词
doubly fed induction generator (DFIG); low voltage ride through (LVRT); grid defaults; FED INDUCTION GENERATOR; THROUGH ENHANCEMENT; FARMS; POWER; OPERATION; SYSTEM;
D O I
10.3390/en6031181
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper presents an improved control strategy for both the rotor side converter (RSC) and grid side converter (GSC) of a doubly fed induction generator (DFIG)-based wind turbine (WT) system to enhance the low voltage ride through (LVRT) capability. Within the proposed control strategy, the RSC control introduces transient feed-forward compensation terms to mitigate the high frequency harmonic components and reduce the surge in the rotor currents. The proposed GSC control scheme also introduces a compensation term reflecting the instantaneous variation of the output power of the rotor side converter with consideration of the instantaneous power of grid filter impendence to keep the dc-link voltage nearly constant during the grid faults. To provide precise control, non-ideal proportional resonant (PR) controllers for both the RSC and GSC current regulation are employed to further improve dynamic performance. Simulations performed in Matlab/ Simulink verify the effectiveness of the proposed control strategy.
引用
收藏
页码:1181 / 1197
页数:17
相关论文
共 28 条
  • [21] Control of a doubly fed induction generator in a wind turbine during grid fault ride-through
    Xiang, Dawei
    Ran, Li
    Tavner, Peter J.
    Yang, Shunchang
    [J]. IEEE TRANSACTIONS ON ENERGY CONVERSION, 2006, 21 (03) : 652 - 662
  • [22] Dynamic modeling and control of DFIG-based wind turbines under, unbalanced network conditions
    Xu, Lie
    Wang, Yi
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2007, 22 (01) : 314 - 323
  • [23] Enhanced Control and Operation of DFIG-Based Wind Farms During Network Unbalance
    Xu, Lie
    [J]. IEEE TRANSACTIONS ON ENERGY CONVERSION, 2008, 23 (04) : 1073 - 1081
  • [24] A Series-Dynamic-Resistor-Based Converter Protection Scheme for Doubly-Fed Induction Generator During Various Fault Conditions
    Yang, Jin
    Fletcher, John E.
    O'Reilly, John
    [J]. IEEE TRANSACTIONS ON ENERGY CONVERSION, 2010, 25 (02) : 422 - 432
  • [25] Advanced Control Strategy of DFIG Wind Turbines for Power System Fault Ride Through
    Yang, Lihui
    Xu, Zhao
    Ostergaard, Jacob
    Dong, Zhao Yang
    Wong, Kit Po
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2012, 27 (02) : 713 - 722
  • [26] An improved control strategy of limiting the dc-link voltage fluctuation for a doubly fed induction wind generator
    Yao, Jun
    Li, Hui
    Liao, Yong
    Chen, Zhe
    [J]. IEEE TRANSACTIONS ON POWER ELECTRONICS, 2008, 23 (03) : 1205 - 1213
  • [27] Zhang W., 2008, P INT C EL MACH SYST
  • [28] Zhang Zhongxiang, 2010, CATAL COMMUN, V53, P12