Optimal maintenance scheduling in a parallel redundant system consisting of series components in each branch

被引:12
作者
Billinton, R [1 ]
Pan, J [1 ]
机构
[1] Univ Saskatchewan, Power Syst Res Grp, Saskatoon, SK S7N 0W0, Canada
关键词
D O I
10.1109/61.772336
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A set of equations is developed in this paper and used in conjunction with the minimal cut set method [1] to evaluate the total failure frequency of a parallel redundant system consisting of series components in each branch where each component can operate in its wearout period and the failure rate of each component is not constant. The optimum maintenance intervals are determined based on the criterion that the total failure frequency of the system is minimized. The Newton-Raphson method is applied to obtain the unknown optimum maintenance intervals for the system. The proposed approach is presented and illustrated using a practical substation example.
引用
收藏
页码:928 / 933
页数:6
相关论文
共 9 条
  • [1] ANDERS GJ, 1990, IEEE T ENERGY CONVER, V5
  • [2] BILLINTON R, 1984, RELIABILITY EVALUAIT
  • [3] BILLINTON ROY., 1983, Reliability Evaluation of Engineering Systems
  • [4] CHRISTENSEN GS, 1987, OPTIMAL CONTROL APPL
  • [5] COFFMAN EG, IEEE T RELIABILITY, V39
  • [6] GHAJAR R, TRANSMISSION RELIABI
  • [7] MICHAEL A, 1989, IEEE T RELIABILITY, V38
  • [8] NELSON WB, 70C211 GEN EL RES DE
  • [9] Zheng X., 1991, IEEE T RELIABILITY, V40