CFD Study on the Air-Side Thermo-Hydraulic Performance for Micro-Channel Heat Exchangers with Louver Pitch Variation

被引:0
|
作者
Saleem, Arslan [1 ]
Kim, Man-Hoe [2 ]
机构
[1] Kyungpook Natl Univ, Dept Mech Engn, Daegu, South Korea
[2] Kyungpook Natl Univ, Sch Mechn Engn, Daegu, South Korea
来源
6TH INTERNATIONAL CONFERENCE ON ENERGY RESEARCH AND DEVELOPMENT | 2016年
关键词
FLAT-TUBE; FLOW;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
A computational study on air-side thermo-hudraulic performance for micro-channel heat exchangers is performed. In order to analyze the air-side thermal hydraulic performance a detailed computational study was performed over Reynolds number range of 35 to 300. The computional analysis was performed using the commonly used parameters of the commercially used heat exchangers in automotive industry. The parameters like flow depth, louver angle, fin pitch and louver height were kept constant and are 20mm (78.7in), 27 degrees (0.47rad), 1.4mm (0.055in) and 6.4mm (0.252in) respectively, while the louver pitch was varied from 1.5mm (0.059in) to 1.9mm (0.075in). The computational results of air-side heat transfer coefficient and pressure drop across the louvered fin are reported in terms of Colburn j-factor and fanning friction f-factor. The trend of change in the air-side heat transfer coefficient and pressure drop associated with the change in louver pitch is also observed and reported. Critical Reynolds number is also obersed and its variation with the change in louver pitch is also reported. The results extracted from the performed analysis are also compared with the previous studies.