Reduction of Airborne Bacterial Burden in the OR by Installation of Unidirectional Displacement Airflow (UDF) Systems

被引:27
作者
Fischer, Sebastian [1 ]
Thieves, Martin [2 ]
Hirsch, Tobias [3 ]
Fischer, Klaus-Dieter [1 ]
Hubert, Helmine [4 ]
Bepler, Steffen [4 ]
Seipp, Hans-Martin [4 ]
机构
[1] Heidelberg Univ, Dept Hand Plast & Reconstruct Surg, Burn Ctr, BG Trauma Ctr Ludwigshafen, Ludwigshafen, Germany
[2] Darmstadt Clin, Div Hosp Hyg, Darmstadt, Germany
[3] Ruhr Univ Bochum, Dept Plast & Reconstruct Surg, Burn Ctr, BG Univ Hosp Bergmannsheil, Bochum, Germany
[4] Univ Appl Sci, Dept Hyg, Giessen, Germany
来源
MEDICAL SCIENCE MONITOR | 2015年 / 21卷
关键词
Environment; Controlled; Operating Rooms; Ventilation; OPERATING-ROOM; CONTAMINATION; JOINT;
D O I
10.12659/MSM.894251
中图分类号
R-3 [医学研究方法]; R3 [基础医学];
学科分类号
1001 ;
摘要
Background: Intraoperative bacterial contamination is a major risk factor for postoperative wound infections. This study investigated the influence type of ventilation system on intraoperative airborne bacterial burden before and after installation of unidirectional displacement air flow systems. Material/Methods: We microbiologically monitored 1286 surgeries performed by a single surgical team that moved from operating rooms (ORs) equipped with turbulent mixing ventilation (TMV, according to standard DIN-1946-4 [1999], ORs 1, 2, and 3) to ORs with unidirectional displacement airflow (UDF, according to standard DIN-1946-4, annex D [2008], ORs 7 and 8). The airborne bacteria were collected intraoperatively with sedimentation plates. After incubation for 48 h, we analyzed the average number of bacteria per h, peak values, and correlation to surgery duration. In addition, we compared the last 138 surgeries in ORs 1-3 with the first 138 surgeries in ORs 7 and 8. Results: Intraoperative airborne bacterial burden was 5.4 CFU/h, 5.5 CFU/h, and 6.1 CFU/h in ORs 1, 2, and 3, respectively. Peak values of burden were 10.7 CFU/h, 11.1 CFU/h, and 11.0 CFU/h in ORs 1, 2, and 3, respectively). With the UDF system, the intraoperative airborne bacterial burden was reduced to 0.21 CFU/h (OR 7) and 0.35 CFU/h (OR 8) on average (p<0.01). Accordingly, peak values decreased to 0.9 CFU/h and 1.0 CFU/h in ORs 7 and 8, respectively (p<0.01). Airborne bacterial burden increased linearly with surgery duration in ORs 1-3, but the UDF system in ORs 7 and 8 kept bacterial levels constantly low (<3 CFU/h). A comparison of the last 138 surgeries before with the first 138 surgeries after changing ORs revealed a 94% reduction in average airborne bacterial burden (5 CFU/h vs. 0.29 CFU/h, p<0.01). Conclusions: The unidirectional displacement airflow, which fulfills the requirements of standard DIN-1946-4 annex D of 2008, is an effective ventilation system that reduces airborne bacterial burden under real clinical conditions by more than 90%. Although decreased postoperative wound infection incidence was not specifically assessed, it is clear that airborne microbiological burden contributes to surgical infections.
引用
收藏
页码:2367 / 2374
页数:8
相关论文
共 19 条
[1]  
[Anonymous], 2003, 14698 ISO DIN 1
[2]  
[Anonymous], 1999, 1946 DIN 4
[3]  
[Anonymous], 2006, 14644 ISO DIN 3
[4]  
[Anonymous], 2007, GERM HLTH REP DIAB 2
[5]  
[Anonymous], 2000, FEDERAL HLTH B HLTH, V43, P644
[6]  
Cecsey, 1996, 13 INT S CONT CONTR
[7]  
CEN, 2000, VENT BUILD TEST PROC
[8]   POSTOPERATIVE INFECTION IN TOTAL PROSTHETIC REPLACEMENT ARTHROPLASTY OF HIP-JOINT WITH SPECIAL REFERENCE TO BACTERIAL CONTENT OF AIR OF OPERATING ROOM [J].
CHARNLEY, J ;
EFTEKHAR, N .
BRITISH JOURNAL OF SURGERY, 1969, 56 (09) :641-+
[9]   Optimisation of ultraclean air - The role of instrument preparation [J].
Chosky, SA ;
Modha, D ;
Taylor, GJS .
JOURNAL OF BONE AND JOINT SURGERY-BRITISH VOLUME, 1996, 78B (05) :835-837
[10]  
Deutsches Institut fur Normung, 2008, 1946 DIN 4