Investigation of the Electric Field of Metallic Fence under a High Voltage Transmission Line

被引:1
|
作者
Virbalis, Juozapas Arvydas [1 ]
Lukocius, Robertas [1 ]
Marciulionis, Povilas [1 ]
Nedzinskaite, Gabija [1 ]
Vaskys, Paulius [1 ]
机构
[1] Kaunas Univ Technol, Dept Elect Power Syst, Studentu St 48-230, LT-51367 Kaunas, Lithuania
关键词
Effective value; electric field strength; high voltage power line; fence; open switch-gear; MAGNETIC-FIELDS; POWER-LINE; SUBSTATIONS; INDUCTION;
D O I
10.5755/j01.eie.22.6.17218
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
There could be areas near a high voltage power transmission lines where electric field strength can exceed maximum permissible values and could be harmful to workers. Territory of the open switch-gear with a metallic fence can be dangerous especially because the power line wires there are at a relatively low height. Therefore, it is important to know surely what the values of electric field strength are near a fence. The expressions for calculation of electric field strength at any observation point near the three-phase line with near the line set metallic fence dependently on the geometrical parameters of line and fence and the coordinates of observation point are presented in the paper. 2D approach is applied to implement the task. Values of electric field strength, obtained applying the analytical method, were compared with the numerically calculated ones. The comparison showed that difference between results obtained by analytical calculations and results obtained by numerical modelling is not greater than 10%. The results show that there is some area near the fence in which the electric field strength exceeds permissible values.
引用
收藏
页码:22 / 27
页数:6
相关论文
共 50 条
  • [1] Electric Field Calculation of High Voltage Transmission Line
    Lu, Yong
    PIERS 2009 MOSCOW VOLS I AND II, PROCEEDINGS, 2009, : 624 - 627
  • [2] Mathematical models for electric field under high voltage overhead line
    Zhang, Qichun
    Ruan, Jiangjun
    Yu, Jianhui
    Gaodianya Jishu/High Voltage Engineering, 2000, 26 (01): : 19 - 21
  • [3] Research on electric field of high-voltage transmission line power frequency
    Xu, Luwen
    Li, Yongming
    Yu, Jihui
    Hou, Xingzhe
    An, Changping
    2006 INTERNATIONAL CONFERENCE ON POWER SYSTEMS TECHNOLOGY: POWERCON, VOLS 1- 6, 2006, : 1381 - +
  • [4] Electric Field Calculation on Surface of High-Voltage Transmission Line Conductors
    Carsimamovic, A.
    Mujezinovic, A.
    Carsimamovic, S.
    Bajramovic, Z.
    Kosarac, M.
    ADVANCED TECHNOLOGIES, SYSTEMS, AND APPLICATIONS II, 2018, 28 : 941 - 951
  • [5] Numerical Determination of electric field induced currents on human body Standing under a high voltage transmission line
    El-Makkawy, S. M.
    2007 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2007, : 802 - 806
  • [6] Methods of electric field intensity reduction under overhead electric power transmission lines of high voltage
    Oleszkiewicz, Pawel
    Nadolny, Zbigniew
    PRZEGLAD ELEKTROTECHNICZNY, 2010, 86 (05): : 196 - 199
  • [7] Analysis of electric field influence on buildings under high-voltage transmission lines
    Tong, Ziyuan
    Dong, Zhaoyang
    Ashton, Trevor
    IET SCIENCE MEASUREMENT & TECHNOLOGY, 2016, 10 (04) : 253 - 258
  • [8] Calculation of the Surface Electric Field Distribution of High-Voltage Direct Current Transmission Line
    Hao J.
    Wang H.
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2019, 34 : 14 - 21
  • [9] Analysis of Electric Melting Ice on High Voltage Transmission Line
    Lv, Xifeng
    He, Qing
    Chang, Ze
    Zhao, Xiaotong
    INTERNATIONAL CONFERENCE ON FRONTIERS OF ENVIRONMENT, ENERGY AND BIOSCIENCE (ICFEEB 2013), 2013, : 283 - 288
  • [10] Computation of electric field induced currents on human body standing under a high voltage transmission line by using charge simulation method
    Yildirim, H
    Kalenderli, O
    PROCEEDINGS OF THE 1998 2ND INTERNATIONAL CONFERENCE BIOMEDICAL ENGINEERING DAYS, 1998, : 75 - 77